Installation Manual
72
61601101901
Leaving Air Sensor
LAS Heating Lockout - 120° - 200° F (180°F default)
LAS Cooling Lockout – 40° – 60°F (45°F default)
Disable Zoning
Zoning Enabled – Zoning system operates normally.
NOTE: Leaving air sensor must be installed for proper oper-
ation of zoning system.
Zoning Disabled – Zoning operation is disabled. All
dampers are driven to the open position. Temperature is
controlled by the main Observer
®
Wall Control. Zone sen-
sors are not used to control temperature when zoning is dis-
abled.