Installation Manual
15
616 01 1019 01
Check Equipment
Inspect equipment. File claim with shipping company prior to
installation if shipment is damaged or incomplete.
Location
All wiring must comply with national, local, and state codes.
Wall Control
The Observer
®
Control is the command center for the com-
municating system. It should be located where it is easily
accessible and visible to the adult homeowner or end user.
For accurate temperature measurement, the following
guidelines should be followed:
The Observer Control and Room Sensors SHOULD be
mounted:
Approximately 5-ft (1.5 m) from the floor.
Close to or in a frequently used room, preferably on an inside
partitioning wall.
On a section of wall without pipes or ductwork.
The Observer Control and Room Sensors SHOULD NOT be
mounted:
Close to a window, on an outside wall, or next to a door lead-
ingtotheoutside.
Exposed to direct light or heat from a lamp, sun, fireplace, or
other temperature-radiating objects which could cause a false
reading.
Close to or in direct airflow from supply registers.
In areas with poor air circulation, such as behind a door or in
an alcove.