Status Code Recall Mode
Active status codes are stored in memory even when power is
absent. The most recently flashing status code (highest priority
active) can be recalled from memory via status code recall mode
and displayed using the amber LED. The status code recall mode is
accessed by shorting (use a clip wire) the “force defrost” connector
(labeled J2 on the board) and then power ON the unit. Please make
sure the unit is turned OFF before shorting the pins. Status call
recall mode will continue as long as the “force defrost” terminals
remain shorted. The unit will not attempt to heat or cool while the
terminals remain shorted. Once the status code is read, power down
the unit and remove the short.
Table 6 – Troubleshooting
A170002
FINAL CHECKS
IMPORTANT: Before leaving job, be sure to do the
following:
1. Ensure that all wiring is routed away from tubing
and sheet metal edges to prevent rub - through or
wire pinching.
2. Ensure that all wiring and tubing is secure in unit
before adding panels and covers. Securely fasten
all panels and covers.
3. Tighten service valve stem caps to 1/12- turn past
finger tight.
4. Leave User’s Manual with owner. Explain system
operation and periodic maintenance requirements
outlined in manual.
CARE AND MAINTENANCE
For continuing high performance and to minimize
possible equipment failure, periodic maintenance must be
performed on this equipment.
Frequency of maintenance may vary depending upon
geographic areas, such as coastal applications. See
Owner’s Manual for information.