Specifications

Specifications subject to change without notice.
616 51 1003 01
3
WIRING REQUIREMENTS ZONING PANEL AND SYSTEM
Logic Power Supply and Communications
DX+, DX, R, C from indoor unit
NOTE: the requirement for the R wire (24vac) may be replaced by an
independent transformer for the zoning communication bus, see below
Zoning Power Supply
Class 2, 24volt 75 VA maximum (sufficient to power all dampers);
recommend second fieldsupplied transformer for communication bus, when
multiple CTS are used as zone sensors, or zone panel reports low voltage
fault. See Zone Panel Installation Instructions
Wiring Material
Standard thermostat wire, 18 AWG recommended; smaller gauge wire may
cause operational and bus communication issues
ZONING ACCESSORIES
Part Number Description
ZONE0101ZP6
Observer Zone Panel supports up to 6 zones and provides basic relay logic for damper operation
and serves as the common connection point for the Observer Zoning System.
ZONE0101RRS
Observer Communicating Room Sensor is a Zone Sensor option for Zones 2 through 6. It provides
full setback capabilities (through the Observer wall control interface only) and communicates to Ob-
server Zoning System).
ZONEXX0DTS01
REQUIRED FOR ALL ZONING SYSTEMS: Leaving Air Temperature (LAT) Sensor provides temper-
ature readings to the zoning system to optimize performance and to protect the equipment
ZDAMPRND06INCB Round Dampers 6 inch power open, power closed damper with self-aligning shaft and actuator hub
ZDAMPRND08INCB Round Dampers 8 inch power open, power closed damper with self-aligning shaft and actuator hub
ZDAMPRND10INCB Round Dampers 10 inch power open, power closed damper with self-aligning shaft and actuator hub
ZDAMPRND12INCB Round Dampers 12 inch power open, power closed damper with self-aligning shaft and actuator hub
ZDAMPRND14INCB Round Dampers 14 inch power open, power closed damper with self-aligning shaft and actuator hub
ZDAMPRND16INCB Round Dampers 16 inch power open, power closed damper with self-aligning shaft and actuator hub
ZDAMPREC08X10B
Rectangular Dampers 8 inch X 10 inch power open, power closed damper
with self-aligning shaft and actuator hub
ZDAMPREC08X14B
Rectangular Dampers 8 inch X 14 inch power open, power closed damper
with self-aligning shaft and actuator hub
ZDAMPREC08X18B
Rectangular Dampers 8 inch X 18 inch power open, power closed damper
with self-aligning shaft and actuator hub
ZDAMPREC08X24B
Rectangular Dampers 8 inch X 24 inch power open, power closed damper
with self-aligning shaft and actuator hub
ZDAMPREC10X10B
Rectangular Dampers 10 inch X 10 inch power open, power closed damper
with self-aligning shaft and actuator hub
ZDAMPREC10X14B
Rectangular Dampers 10 inch X 14 inch power open, power closed damper
with self-aligning shaft and actuator hub
ZDAMPREC10X18B
Rectangular Dampers 10 inch X 18 inch power open, power closed damper
with self-aligning shaft and actuator hub
ZDAMPREC10X24B
Rectangular Dampers 10 inch X 24 inch power open, power closed damper
with self-aligning shaft and actuator hub
ZDAMPBAR08X14
Rectangular Barometric Bypass 8 inch X 14 inch power open, power closed damper
with self-aligning shaft and actuator hub
ZDAMPBAR08X24
Rectangular Barometric Bypass 8 inch X 24 inch power open, power closed damper
with self-aligning shaft and actuator hub
ZDAMPACT45DEGR 45 Replacement Actuator for Round Dampers
ZDAMPACT90DEGR 90 Replacement Actuator for Round Dampers
Notes for NonICP Damper Requirements:
1. Dampers may be power open / power close or spring open / power closed.
2. Power Open / Power Close will be 3 terminals: OPEN / CLOSE / COMMON
3. Drive times are controlled through the OBSERVERr set up will be: 15, 30, 45, 50, 75, 105 and 120 seconds
4. No more than 3 dampers, wired in parallel, per zone
5. Total load for ZONE0101ZP6 is 75VA (3 amps) total. No more than 48VA (2 amps) per single zone.
(Class 2 systems only allow a maximum of 75VA for the circuits.)