Installation Manual
73
616 01 1019 01
Damper Timing
Selects the drive time for the dampers. Selections are 15,
30, 45, 60, 75, 105, and 120 seconds.
NOTE: Verify damper manufacturer opening/closing timing
requirements.
DISABLED (Default)
LOW
MEDIUM
HIGH
Heat Recovery Maintenance
Energizes the fan output at the specified speed for HRV
applications
Stage Li miting for Multistage Units
For Multistage units there are, dealer selectable minimum
and maximum, stage limits for both heating and cooling.
Associated with the each minimum limit is a threshold
outdoor air temperature beyond which the minimum stage
limit is active.