TECHNICAL SUPPORT MANUAL Split System Heat Pump: (H,C,T)CH(6)
10 428 04 170100
MULTIPLYING FACTORS
Total capacities are net (I.D. blower heat subtracted) system capacities based on 25 foot (7.62m) line set.
If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may
occur.
†† At TVA rating indoor condition (75°F db, 63°Fwb), all other indoor air temperatures are at 80° Fdb
If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may
occur.
* System amps are total of indoor and outdoor amps.
Chart data is for 80° F indoor dry bulb. For indoor db temperatures other than 80° F, measure Indoor db and
Indoor CFM, and plug these into the
formula below. Measure outdoor db and indoor wet bulb, apply these to the chart above, find MBh and S/T,
and plug these into the formula below.
(Note: if indoor db is the only thing changing, total capacity, MBh, stays the same.)
Sensible Capacity at Indoor db LOWER than 80° F=(
MBh x S/T ) --
( 80 -- Indoor db ) x 835 x Indoor CFM
1000
(
)
Sensible Capacity at Indoor db HIGHER than 80° F=(
MBh x S/T
)+
( Indoor db -- 80 ) x 835 x Indoor CFM
1000
(
)