Specifications
PRODUCT SPECIFICATIONS Vertical Evaporator Coils: END4X, ENW4X, ENA4X
12 484 51 3601 01
Specifications subject to change without notice.
NOTES:
1. Contact manufacturer for cooling capacities at conditions other than shown in table.
2. Formulas:
Leaving db = entering db −
sensible
heat
cap.
1.09
x
CFM
Leaving wb = wb corresponding to enthalpy of air leaving coil (h
LWB
)
h
LWB
= h
EWB
−
total
capacity
(Btuh)
4.5
x
CFM
Where h
EWB
= enthalpy of air entering coil
3. SHC is based on 80F (27C) db temperature of air entering the evaporator coil.
Below 80F (27C) db, subtract (Correction Factor x CFM) from SHC.
Above 80F (27C) db, add (Correction Factor x CFM) to SHC.
4. Direct interpolation is permissible. Do not extrapolate.
5. Fan motor heat has not been deducted.
6. All data points are based on 10F (−12C) superheat leaving coil and use of thermostatic expansion valve (TXV) device.
7. The END4X, ENW4X, and ENA4X coils can be used in any properly designed system using R−410A refrigerant.
8. Before using maximum cfm shown in table, check coil static pressure drop to ensure system blower can provide necessary static pressure needed
for coil and duct systems.
9. Bypass Factor = 0 indicates no psychometric solution. Use bypass factor of next lower EWB for approximation.
BYPASS FACTOR
ENTERING AIR DRY BULB TEMPERATURE _F (_C)
79 (26) 78 (26) 77 (25) 76 (24) 75 (24) Under 75 (24)
81 (27) 82 (28) 83 (28) 84 (29) 84 (29) Above 85 (29)
Correction Factor
0.10 0.98 1.96 2.94 3.92 4.91
Use formula shown below
0.20 0.87 1.74 2.62 3.49 4.36
0.30 0.76 1.53 2.29 3.05 3.82
Interpolation is permissible.
Correction Factor = 1.09 x (1 − BF) x (db − 80)