Installation Manual

2 484 01 3905 03
Specifications subject to change without notice.
IMPORTANT: Nitrogen can leak out through the hole that the
needle pierced in the plugs. This does not indicate a leaking
coil nor warrant return of the coil.
INTRODUCTION
Use this instruction manual to install EAM4X & WLAM indoor
coils on multipoise furnaces. EAM4X & WLAM models are
enclosed in a casing.
Table 1
COIL INFORMATION
Model Number Tons
Flush to fit
Furnace
width
Coil Connection
Tube Size
inches
inches (mm) Liquid
Suc -
tion
EAM4X18L14A 1 1/2 143/16 (360) 3/8 5/8
EAM4X19L17A 1 1/2 171/2 (445) 3/8 3/4
EAM4X24L14A 2 143/16 (360) 3/8 5/8
EAM4X24L17A 2 171/2 (445) 3/8 5/8
EAM4X25L17A 2 171/2 (445) 3/8 3/4
EAM4X30L14A 2 1/2 143/16 (360) 3/8 3/4
EAM4X30L17A 2 1/2 171/2 (445) 3/8 3/4
EAM4X36L14A 3 143/16 (360) 3/8 3/4
EAM4X36L17A 3 171/2 (445) 3/8 3/4
EAM4X36L21A 3 21 (533) 3/8 3/4
EAM4X37L17A 3 171/2 (445) 3/8 3/4
EAM4X37L21A 3 21 (533) 3/8 7/8
EAM4X42L21A 3 1/2 21 (533) 3/8 7/8
EAM4X42L24A 3 1/2 241/2 (622) 3/8 7/8
EAM4X43L21A 3 1/2 21 (533) 3/8 7/8
EAM4X48L17A 4 171/2 (445) 3/8 7/8
EAM4X48L21A 4 21 (533) 3/8 7/8
EAM4X48L24A 4 241/2 (622) 3/8 7/8
EAM4X60L21A 5 21 (533) 3/8 7/8
EAM4X61L21A 5 21 (533) 3/8 7/8
EAM4X60L24A 5 241/2 (622) 3/8 7/8
EAM4X61L24A 5 241/2 (622) 3/8 7/8
Model Number Tons
Flush to fit
Furnace
width
Coil Connection
Tube Size
inches
WLAM184AA 11/2 143/16 (360) 3/8 5/8
WLAM194BA 11/2 171/2 (445) 3/8 3/4
WLAM244AA 2 143/16 (360) 3/8 5/8
WLAM244BA 2 171/2 (445) 3/8 5/8
WLAM254BA 2 171/2 (445) 3/8 3/4
WLAM304AA 2- 1/2 143/16 (360) 3/8 3/4
WLAM304BA 2- 1/2 171/2 (445) 3/8 3/4
WLAM364BA 3 171/2 (445) 3/8 3/4
WLAM374BA 3 171/2 (445) 3/8 3/4
WLAM374CA 3 21 (533) 3/8 7/8
WLAM424CA 3- 1/2 21 (533) 3/8 7/8
WLAM434CA 3- 1/2 21 (533) 3/8 7/8
WLAM484CA 4 21 (533) 3/8 7/8
WLAM604CA 5 21 (533) 3/8 7/8
WLAM614CA 5 21 (533) 3/8 7/8
WLAM604DA 5 241/2 (622) 3/8 7/8
WLAM614DA 5 241/2 (622) 3/8 7/8
INSTALLATION
INSPECT EQUIPMENT
File claim with shipper if equipment is damaged.
SELECT INSTALLATION
For upflow application follow:
See Table 1 for dimensions. Note instructions for placement of
coil casing on furnace.
Return
Return
Supply
Supply
Evaporator
Coil
Horizontal Left Furnace Installation
Horizontal Right Furnace Installation
A05400
Evaporator
Coil
Return
Return
Supply
Supply
Downflow
Furnace
Installation
Upflow
Furnace
Installation
A05401
Figure 1 - Typical Coi l Instal l at ion on Furnace
INSTALLATION OF EVAPORATOR COILS
Upflow coil installation
The c ased coil is designed to fit furnaces of the same width.
1. Set c oil in place on upflow furnace discharge air
opening.
2. Ensure coil is level for proper condensate drainage. Do
not tip coil toward condensate drain. Coil casing need
not be fastened or screwed to furnace.
3. When installing wider coil on narrow furnace, create field
fabricated adapter. (See Figure 2)