THE THERMAL EQUALIZER OPERATING AND INSTALLATION MANUAL FOR MODELS 10, 15 & 25.
OPERATING AND INSTALLATION MANUAL 1. Technical information 2. Warranty and Refurbish Program 3. Exploded view of the AIRIUS SYSTEM ® 4. General Installation and Operating guidelines 5. Hanging the AIRIUS SYSTEM 6. Placement of the AIRIUS SYSTEM 7. Suspended Ceiling Kit Assembly Instructions 8.
MODEL NUMBER - SERIAL NUMBER - MANUFACTURE INFORMATION ELECTRICAL INFORMATION HAZARD INFORMATION IS LOCATED ON LABELS AT THE EXAUST END OF THE APPLIANCE (THE MOTOR IS THERMALLY PROTECTED) Model No.@120 VAC = Motor Part No. Hertz Model 25 (7.6M) Model 15 (4.6M) Model 10 (3.0M) = FP-108 HH (S1 B) - 50/60 Hz 30/35 W - 1500/1650 rpm = FP-108 HH (S2 B) - 50/60 Hz 14/17W - 1100/1250 rpm = FP-108 HH (S3 B) - 50/60 Hz 13/15W - 900/1080 rpm Model No.@230 VAC = Motor Part No. Model 25 (7.6M) Model 15 (4.
3. EXPLODED VIEW Voltages - 120 VAC, 230 VAC, 277VAC. Total Height 22” (55.88cm) Width 13” (33.02 cm) Total Weight = 12lb (5.4k) Image not available online. The above graphic contains all the descriptions/components of the AIRIUS SYSTEM models 10, 15, 25 Note: ALL SCREW SIZES ARE ENGLISH THREAD with TORX ¤ HEADS ENGLISH SIZED HEX WRENCHS CAN BE SUBSTITUTED TO OPERATE SCREWS 4.
OUTLET - 120 VAC, 230 VAC and 277 VAC Power Outlets (Female Connectors) to supply power to the AIRIUS SYSTEM should always be installed by a qualified electrician or similarly qualified person in accordance with national and local electrical codes. The AIRIUS SYSTEM uses very little AMPERAGE (less than 1 amp) thus multiple outlets may be installed on one circuit. Outlets are available in many configurations, check with the local Electrical Contractor to determine preferred type for the facility.
Always hold the AIRIUS SYSTEM unit by the Bail/Crosspiece to avoid injury from moving parts. To confirm electrical continuity, if possible, Plug the AIRIUS SYSTEM into a energized outlet, similar to the outlet installed in the ceiling, on the ground before permanently mounting the AIRIUS SYSTEM in the ceiling. NOTE: The AIRIUS SYSTEM can be wired directly to a junction box but only by a qualified electrician or similarly qualified person.
power cord. The following graphic is an example of the typical AIRIUS SYSTEM: THE AIRIUS SYSTEM HANGING/MOUNTING GUIDELINES Locking nuts, washers or beam clamp Cord Secured RSJ or Ceiling Beam Intake Receptical Rated 120 or 230 VAC (277 VAC) Swivel FOR BEST EFFICIENCY The AIRIUS SYSTEM should be securely installed as close as possible to the ceiling. The AIRIUS SYSTEM air column should have an unobstructed passage to the floor.
Machinery - Machinery and work processes that are sensitive to temperature change will operate much more efficiently when the AIRIUS SYSTEM is operating. The flow of air should be directed to a place that will allow circulation but not interfere with the production process. People - Most people are not comfortable in direct air flow, therefore the AIRIUS SYSTEM can be directed to a space near the person, but not directly on them. This balanced, equalised air will provide a better working environment.
8. THE AIRIUS SYSTEM SAFETY INFORMATION AND WARNING! EACH AIRIUS SYSTEM HAS A POLARIZED/GROUNDED PLUG TO REDUCE THE RISK OF ELECTRICAL SHOCK (NOT FITTED ON UNITS SENT TO EUROPE/MIDDLE EAST - SEE WIRING INSTRUCTIONS). THIS PLUG CAN ONLY FIT INTO THE DESIGNED POLARIZED/GROUNDED OUTLET ONE WAY. IF THE PLUG DOES NOT FIT FULLY IN THE OUTLET, CONTACT A QUALIFIED ELECTRICIAN. DO NOT ATTEMPT TO OVERCOME THIS SAFETY FEATURE.
THE MOTOR IS THERMALLY PROTECTED; OVERHEATING (230F/110C) WILL CAUSE THE MOTOR TO STOP OPERATING. THE MOTOR MAY RESTART ONCE NORMAL OPERATING TEMPERATURES (195F/90C) ARE ACHIEVED. IF MOTOR FAILS TO RESTART: • DISCONNECT MOTOR FROM ELECTRIC SOURCE AND CONTACT MANUFACTURER OR ITS AGENT DO NOT POSTION SYSTEM NEAR: • • • • FURNACES, FIREPLACES, STOVES, OR OTHER HIGH TEMPERATURE HEAT SOURCES. DO NOT POSITION PRODUCT UNDER INFRA-RED HEAT SOURCES.
• DO NOT USE PETROLEUM PRODUCTS, THINNERS, SOLVENTS, AMMONIAS, ALCOHOLS, OR OTHER CHEMICALS, TO CLEAN ANY PART OF THE AIRIUS SYSTEM THE PERFORMANCE AND RESULTS OF THE AIRIUS SYSTEMS® SYSTEM ARE SUBJECT TO MANY VARIABLES SUCH AS, BUT NOT LIMITED TO, THE INTERIOR ENVIRONMENT, EXTERIOR ENVIRONMENT, CONDITION OF BUILDING STRUCTURE, HVAC SYSTEM PERFORMANCE AND/OR ELECTRICAL SERVICE AND THUS ACTUAL RESULTS MAY VERY.