12.2 Fault codes
The fault codes can be useful in case of malfunction of the DFGT. Table below contains an overview of all possible
fault codes, their cause and possible action to solve the problem. The actual value of the fault (Table 7) can be
read by the DFRC, DFRC-SE, BRDG and BLE device. The ESYS fault (Table 7 and 8) can also be read by the
DFRC using setting Tag 57.
Tag
Name
Min
Max
Step
Default
Unit
Remarks
57
Display ESYS fault
0
1
1
1
-
0 = ESYS fault is not
displayed on DFRC
1 = ESYS fault and fault
code are alternately
displayed on DFRC in case
of a fault
Table 7: Fault Code Description
Tag
Fault
code
Fault type
ESYS
Fault
Action
F100
1
ESYS communication failure
-
F101
2
Internal Temperature to high
-
Check if the ventilation slots of the
DFGT are not blocked. Check if
there is enough free space around
the DFGT. Check if there is enough
air flow to cool the electronics
F102
3
Wired room sensor NTC fault
-
Check the wiring of the sensor
Replace the sensor if needed.
F103
4
Wired outside sensor NTC fault
-
Check the wiring of the sensor
Replace the sensor if needed.
F104
5
RF communication timeout with
DFRC
-
Check the communication with the
remote control. The remote control
must be nearby
F105
6
RF communication timeout with
BRDG
Check the communication with the
BRDG.
F106
7
No flame and no fault feedback from
ESYS (timeout on flame)
-
Check the ionization
F107
8
ESYS error and flame not detected
1,2,3,8,27
F108
9
Disable contact closed (user must
manually close contact)
50
Enable contact
F109
10
ESYS error when mode is Pilot on for
less than 30 minutes
1,27