Quick Start Guide
Quick Start Guide – DFGT-03MCXXX
Copyright © 2021 Airios. All rights reserved.
Airios Confidential and Proprietary Revision 15 – Draft Page 18 of 59
4 Control
4.1 Temperature control
Temperature control is not allowed in an open decorative fire.
Tag
Name
Min
Max
Step
Default
Unit
Remarks
22
Open closed
0
255
1
255
-
0 – Open (not allowed)
1 – Closed
255 – Not Configured
Should be set to 0 or 1
after product is
configured
(Settings above)
30
Temperature control available
0
1
1
0
-
Setpoint of temperature control can be set by either the DFRC, Gateway or app (only DFGT-03MCB23).
The measured temperature can be from:
1. Connected NTC sensor. See Appendix A for setting on I/O and par 3.1.1 Description connections for
connecting the NTC sensor.
2. DFRC
The DFGT uses its own measured temperature (NTC, connected on I/O2 or I/O3) in case this input (room temp,
see setting below)) is selected during configuration and this temperature is valid (0..45°C), otherwise the DFRC
temperature is used.
NTC connected to I/O2
Tag
Name
Min
Max
Step
Value
Remarks
42001
Input 2 function
0
19
1
16
Room temp
NTC connected to I/O3
Tag
Name
Min
Max
Step
Value
Remarks
42002
Input 3 function
0
19
1
16
Room temp
4.2 User interface
4.2.1 Push Button
The PCB itself contains the so-called internal push button. An external push button can be connected to the
connector terminals (JP1) on the PCB. Both internal and external push button operates in the same way.