3.3.2.2 Standing pilot (SP)
When a pilot flame is available, the standing pilot setting should be configured. This allows ignition of the main
burner through the pilot flame. The pilot flame itself can also be controlled to be on or off. A secondary burner can
also be configured.
Tag
Name
Min
Max
Step
Default
Unit
Remarks
20
Secondary burner available
0
1
1
0
-
For second burner available
set to ‘1’
21
Standing pilot available
0
1
1
0
-
For SP application set to ‘1
23
Enable secondary burner on
when main burner on
0
1
1
0
-
0 On ignition only main is
switched on
1 On ignition main and
second are switch on in
sequence
2 On ignition main and
second are ignited (even if
second is not switched on)
Figure 7: Ignition sequence one burner