Quick Start Guide

Quick Start Guide DFGT-03MCXXX
Copyright © 2021 Airios. All rights reserved.
Airios Confidential and Proprietary Revision 15 Draft Page 12 of 59
3.3.1 Burner settings
The following settings should be configured for the fireplace burner configuration.
Tag
Name
Min
Max
Step
Default
Unit
Remarks
1
Minimum current
45
250
1
45
mA
The current that is needed
to set the gas valve in the
position according to the
required minimum flame
height.
2
Maximum current
45
250
1
250
mA
The current that is needed
to set the gas valve in the
position according to the
required maximum flame
height.
3
Start current main gas valve
45
250
1
215
mA
The current that is needed
to set the gas valve in the
ignition position. This
current is not limited by the
minimum and maximum
flame height currents
4
Start current second gas valve
45
250
1
215
mA
The current that is needed
to set the gas valve in the
ignition position for the
second burner. This
current is not limited by the
minimum and maximum
flame height currents
5
Start time main gas valve
0
240
1
30
s
The time it takes to ignite
the main burner.
6
Start time second gas valve
0
240
1
10
s
The time it takes to ignite
the second burner.
7
Max Time Ignite State
60
240
1
240
s
After ignition, a flame must be
detected within the set time. If
not, the gas valve will be
closed and there will be an
error indication on both the
user interface of the DFGT
and the Remote Control of
the decorative fire. The user
has to ignite the decorative
fire again.
The value must be chosen in
such a way that the time is
sufficient for fireplace to run a
complete start cyclus