General Description
OPTIONAL EXTRAS - GENERAL
This feature is included as part of the Intelligent Head Pressure Control option, as
detailed above and comes as standard when the EEV options is selected.
Specifically designed for night time operation as optimum low noise levels are achieved
with reduced ambient temperature and room loads, this feature is also ideal for residential
and other outdoor noise critical applications.
Low Noise Feature for
Condenser Fan
(A & X Models)
Initiated by setting the microprocessor programmable time clock, the head pressure set
point changes from the standard 14 Barg (203 psig) to 22 Barg (319 psig), reducing the
outdoor unit fan speed and corresponding operating sound levels.
Humidification is provided by an electrode boiler. The sealed humidifier design ensures
that only clean sterile steam is supplied to the conditioned area and corrosive salts and
minerals are held in the disposable bottle. The steam is distributed through a sparge pipe
fitted to the coil assembly.
Featuring modulating capacity output control as standard, the system provides
continuous modulation of steam output in response to a proportional control signal. The
output control range is 20%-100% of the humidifier rated value and is designed to give an
approximate steam output of +/- 3%, at the sensor, thus ensuring precise control of the
conditioned space.
The cylinder operating life time is automatically optimised via the integrated water
conductivity sensor, which combined with the controls monitors and
regulates the water refill cycle to reduce excessive salt deposits and the progressive wear
of the cylinder. For further details, refer to Design Features & Information.
Humidifier - Intelligent
Modulation
All humidifier parameters and alarms are accessible and adjustable via the
microprocessor display keypad unit, main features include:
· Supply water conductivity (mS/cm)
· Actual steam output (kg/h)
· Required steam output (kg/h)
· Actual current rating (A)
· Required current rating (A)
· Status mode (Start Up, Running, Filling, Draining)
GENERAL