Technical data

Precision Air Conditioning
-
V
Precision Air Conditioning
Technical Manual : 6258867 F 07/2012
73
General Specification - Condensing Units CUS3 - CUS30D
ELECTRICAL DATA
CUS3
CUS4
CUS5
CUS5.5
CUS6
CUS6.5
Unit Data
(1)
Nominal Run Amps A 7.1
9.5
11.1
11.9
13.8
15.7
Maximum Start Amps A 46.6
67.0
71.1
76.1
106.6
104.6
Recommended Mains Fuse Size A 16
20
20
20
25
25
Max Mains Incoming Cable Size mm² 6
6
10
10
10
10
Mains Supply V 400V / 3Ph +N / 50Hz
Control Circuit VAC 230
230
230
230
230
230
Fan - Per Fan
Motor Size kW 0.15
0.15
0.59
0.59
0.59
0.59
Full Load Amps A 0.65
0.65
2.80
2.80
2.80
2.80
Locked Rotor Amps A 2.60
2.60
5.60
5.60
5.60
5.60
Compressor - Per Compressor
Nominal Run Amps (1) A 6.4
8.2
8.3
9.1
11.0
12.9
Locked Rotor Amps A 44
61.8
65.5
70.5
101.0
99.0
Motor Size kW 2.9
4.0
4.45
5.3
5.9
6.65
Oil Sump Heater Rating W N/A
N/A
N/A
N/A
N/A
N/A
Type of Start Direct on Line
CUS7.5
CUS8.5
CUS10
CUS12
CUS30D
Unit Data
(1)
Nominal Run Amps A 15.3
20.1
21.7
28.5
56.8
Maximum Start Amps A 103.6
131.2
131.2
156.2
207.6
Recommended Mains Fuse Size A 25
32
40
40
80
Max Mains Incoming Cable Size mm² 10
10
10
10
35
Mains Supply V 400V / 3Ph +N / 50Hz
Permanent Supply V N/A
N/A
N/A
N/A
230V/ 1PH +N
/ 50Hz
Rec. Permanent Fuse A N/A
N/A
N/A
N/A
4
Max Permanent Incoming Cable
Size
mm² N/A
N/A
N/A
N/A
2.5
Control Circuit VAC 230
230
230
230
24
Fan - Per Fan
Motor Size kW 0.59
0.59
0.59
0.59
0.55
Full Load Amps A 2.80
2.80
2.80
2.80
2.50
Locked Rotor Amps A 5.60
5.60
5.60
5.60
5.80
Compressor - Per Compressor
Nominal Run Amps (1) A 12.5
14.5
16.1
22.9
24.2
Locked Rotor Amps A 98.0
120.0
120.0
145.0
175.0
Motor Size kW 6.84
8.5
8.9
11.84
13.4
Oil Sump Heater Rating W 50
50
50
50
75
Type of Start Direct on Line
(1) Nominal data based on C evaporating temperature and a 35°C ambient.
OUTDOOR UNIT