Technical data

Precision Air Conditioning
-
V
Precision Air Conditioning
Technical Manual : 6258867 F 07/2012
71
Dimensional & Installation Data - Condensers C 11 - 50
DIMENSIONS / WEIGHTS / POSITIONING
Refer to the relevant installation manual for full lifting and positioning information.
IMPORTANT
Unit diagrams can be supplied on request.
C 11 - 50 - Horizontal (mm)
C
G
A
D
(3)
(4a
)
F
B
(4b
)
500
(2)
500
(2)
500
(2)
18
00
(2)
(5)
E
(1)
(1)
(1)
DIMENSIONS (MM) WEIGHTS (KG)
Standard Fan Optional SCAF
(7)
A
B
C
D
E
F
G
B
F
Standard
Fan
Optional
SCAF
C11HI-H
648
550
1275
455
530
550
1118
675
640
51
61
C15HI-H
648
550
1275
455
530
550
1118
675
640
63
73
C20HI-H
848
645
1100
455
530
550
944
735
640
58
70
C25HI-H
848
645
1100
455
530
550
944
735
640
65
77
C35HI-H
1048
645
1650
455
530
550
1494
711
640
97
109
C45HI-H
1048
645
1650
455
530
550
1494
711
640
110
134
CS50HI-H 2184
1167
1000
2121
700
132
145
154
2184
1167
1000
C 11 - 50 - Vertical (mm)
(3)
500mm
(2)
(4
a
)
A
D
18
00
(2)
C
E
B
F
500
(2)
500
(2)
500
(2)
500
(2)
(
5
)
(4
b
)
(1)
(1)
DIMENSIONS (MM) WEIGHTS (KG)
Standard Fan Optional SCAF
(7)
A
B
C
D
E
F
A
Standard
Fan
Optional
SCAF
C11HI-V
997
700
1275
952
630
1118
1112
51
61
C15HI-V
997
700
1275
952
630
1118
1112
63
73
C20HI-V
1092
900
1100
952
830
944
1162
58
70
C25HI-V
1092
900
1100
952
830
944
1162
65
77
C35HI-V
1092
1100
1650
952
1030
1494
1162
97
109
C45HI-V
1092
1100
1650
952
1030
1494
1162
110
134
CS50HI-V
2184
1090
1167
2124
1107
467
1130
1127
132
145
(1) Airflow
(2) Minimum clearances in mm
(3) 8mm fixing points
(4) Service connections to left hand side of the unit: a = Liquid Outlet, b = Discharge Gas Inlet
(5) Mains Electric Isolator, (C50 located behind open side panel)
(6) 4 lifting eye bolts to unit top, size C50
(7) Optional Short Case Axial Fan (SCAF)
CAUTION
A vertical air discharge unit is recommended for installation in windy locations or wherever a
horizontal airflow would be obstructed.
OUTDOOR UNIT