Technical data

Precision Air Conditioning
-
V
Precision Air Conditioning
Technical Manual : 6258867 F 07/2012
7
General Description
STANDARD FEATURES
Airflow Switch
An adjustable differential pressure switch activates a visual alarm at the status panel and
breaks the power supply in the event of a fan or motor failure.
Compressor
(X Models)
Compressor(s) are mounted on the base via the use of vibration isolators. Each
compressor is designed for use with R407C refrigerant.
Utilise hermetic scroll compressors fitted as standard with:
Sizes 9, 13, 19, 23D & 41D
· Internal thermal motor protection
Utilise hermetic scroll compressors fitted as standard with:
· Internal thermal motor protection
Sizes 16, 31 & 35
· ECA Approved
Utilise hermetic scroll compressors fitted as standard with:
· Internal thermal motor protection
· Sight glass
· Internal thermal motor protection
Sizes 23, 25, 50D, 55D, 65D,
80D & 90D
· High discharge gas thermostat
· Oil sump heaters, to guard against refrigerant migration and to eliminate oil foaming
on start-up
Refrigeration
Each refrigeration circuit features as standard:
· Externally equalised thermostatic expansion valve (TEV)
· Sight glass (loose)
A Models
· Filter drier (loose) (supplied with Airedale matched outdoor units)
· Holding charge of inert gas
X Models
· Externally equalised thermostatic expansion valve (TEV)
· Sight glass (loose)
· Filter drier (loose) (supplied with Airedale matched outdoor units)
· Low pressure switch - manual reset
· High pressure switch - manual reset
· Holding charge of inert gas
97mm pleated disposable panel filters in a rigid frame. Conform to BS EN 779-G4.
Access and removal from unit front.
Filters
An adjustable diaphragm pressure switch is fitted across the filter assembly to monitor
pressure drop, which will initiate a filter dirty alarm.
GENERAL