Technical data

-
V
Precision Air Conditioning
Precision Air Conditioning
64
Technical Manual : 6258867 F 07/2012
Design Data - Chilled Water Models
INTERCONNECTING WIRING
L1
¡
ç
L2
¡
ç
L3
¡
ç
N
¡
ç
(1)
INDOOR
UNIT
PE
¡
ç
Mains Incoming Supply 400V / 3PH + N / 50Hz
(1) Although models 9 - 19 are 230V/1/50Hz, a 400/3/50Hz supply is recommended to
accommodate 3ph options, contact Airedale for details.
560
¡
è
Volt Free Alarm N/O
561
¡
ç
Volt Free Alarm Common
562
¡
è
Volt Free Alarm N/C
Common Alarm
563
¡
è
Volt Free Alarm N/O
564
¡
ç
Volt Free Alarm Common
565
¡
è
Volt Free Alarm N/C
Critical Alarm
502
¡
è
Fire Shutdown input
Indoor Controls Only
INDOOR
UNIT
583
¡
ç
Healthy in N/C Condition
502
¡
è
Remote On/Off
INDOOR
UNIT
522
¡
ç
Remote On/OFF
Rx-/Tx-
¡
çè çè ¡
Rx-/Tx-
Rx+/Tx+
¡
çè çè ¡
Rx+/Tx+
Run/Standby Network
INDOOR
UNIT
GND
¡
çè
Use Awg20/22 twisted pair (with overall shield)
cable, Belden ref. 8762 (Airedale ref:
6110316), or equivalent, for
network
çè ¡
GND
INDOOR
UNIT
N + 1
In line with IEE Wiring Regulations, the following should be observed:
· Extra low voltage control cables (ELV) and mains power cable should be segregated by a
minimum distance of 50mm
· If cables must cross, it is recommended that they cross at right angles
CABLE INSTALLATION
· Airedale recommends that ELV cables are screened at one end to earthed enclosures
CHILLED WATER