Technical data

Precision Air Conditioning
-
V
Precision Air Conditioning
Technical Manual : 6258867 F 07/2012
57
General Specification - Chilled Water Models
ELECTRICAL DATA
V9CW
V13CW
V16CW
V19CW
Unit Data
(1)
Nominal Run Amps A 24.2
35.1
35.1
40.3
Maximum Start Amps A 15.3
35.1
35.1
40.3
Recommended Mains Fuse Size A 32
40
40
50
Max Mains Incoming Cable Size mm² 35
35
35
35
Mains Supply (2) V 400V / 3PH + N / 50Hz
Control circuit VAC 24
24
24
24
Evaporator Fan - Per Fan
Quantity / Motor Size kW 1 x 0.60
1 x 0.60
1 x 0.60
1 x 0.74
Full Load Amps A 6.60
6.60
6.60
7.60
Locked Rotor Amps A 16.50
16.50
16.50
19.00
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 1
2
2
2
Number of Elements 3
6
6
6
Rating (Total) kW 7.5
15.0
15.0
15.0
Current Per Phase A 10.9
21.8
21.8
21.8
Humidifier
Capacity kg 0.60 - 3.00
0.60 - 3.00
0.60 - 3.00
1.60 - 8.00
Rating kW 2.25
2.25
2.25
6.00
Full Load Amps A 3.50
3.50
3.50
8.70
HE & Pre Filter Motor Selection
Quantity / Motor Size
kW 1 x 0.60
1 x 0.60
1 x 0.60
1 x 1.10
Full Load Amps A 6.60
6.60
6.60
2.53
Locked Rotor Amps A 16.50
16.50
16.50
16.20
Larger Fan Motor - Per Fan
Quantity / Motor Size kW 1 x 0.75
1 x 0.75
1 x 1.10
1 x 1.10
Full Load Amps A 1.78
1.78
2.53
2.53
Locked Rotor Amps A 11.40
11.40
16.20
16.20
Next Larger Fan Motor - Per Fan
Quantity / Motor Size kW N/A
1 x 1.10
1 x 1.50
1 x 1.50
Full Load Amps A N/A
2.53
3.39
3.39
Locked Rotor Amps A N/A
16.20
23.10
23.10
V23CW
V25CW
V31CW
V35CW
Unit Data
(1)
Nominal Run Amps A 34.4
35.7
37.2
46.2
Maximum Start Amps A 34.4
35.7
43.8
61.4
Recommended Mains Fuse Size A 40
40
50
50
Max Mains Incoming Cable Size mm² 35
35
35
35
Mains Supply (2) V 400V / 3PH + N / 50Hz
Control circuit VAC 24
24
24
24
Evaporator Fan - Per Fan
Quantity / Motor Size kW 1 x 1.5
1 x 2.2
1 x 3.0
1 x 4.0
Full Load Amps A 3.39
4.64
6.18
8.12
Locked Rotor Amps A 23.1
32.5
43.3
60.9
OPTIONAL EXTRAS
Electric Heating
Stage of Reheat 2
2
2
2
Number of Elements 6
6
6
6
Rating (Total) kW 15.0
15.0
15.0
15.0
Current Per Phase A 21.8
21.8
21.8
21.8
Humidifier
Capacity kg 1.6 - 8.0
1.6 - 8.0
1.6 - 8.0
1.6 - 8.0
Rating kW 6.0
6.0
6.0
6.0
Full Load Amps A 8.7
8.7
8.7
8.7
HE & Pre Filter Motor Selection
Quantity / Motor Size
kW 1 x 1.5
1 x 2.2
1 x 4.0
N/A
Full Load Amps A 3.39
4.64
8.12
N/A
Locked Rotor Amps A 23.1
32.5
60.9
N/A
Larger Fan Motor - Per Fan
Quantity / Motor Size kW 1 x 2.2
1 x 3.0
1 x 4.0
N/A
Full Load Amps A 4.64
6.18
8.12
N/A
Locked Rotor Amps A 32.5
43.3
60.9
N/A
Next Larger Fan Motor - Per Fan
Quantity / Motor Size kW 1 x 3.0
N/A
N/A
N/A
Full Load Amps A 6.18
N/A
N/A
N/A
Locked Rotor Amps A 43.3
N/A
N/A
N/A
(1) Values given for full function units (incl. electric heating and humidification) at ARI conditions with EFF1 (IE2) fan motors and standard filters, for
optional data, please contact Airedale.
(2) Although sizes 9 - 19 are 230V/1/50Hz, a 400/3/50Hz supply is recommended to accommodate 3ph options, contact Airedale for details.