Technical data
-
V
Precision Air Conditioning
Precision Air Conditioning
56
Technical Manual : 6258867 F 07/2012
General Specification - Chilled Water Models
MECHANICAL DATA
V65CW
V80CW
V90CW
V95CW
Capacity
(1)
Nom Cooling (Gross) kW 66.3
83.0
91.1
98.1
Fan Gain kW 2 x 1.76
2 x 2.35
2 x 3.24
2 x 3.24
Dimensions - H x D x W
(2) mm 1940 x 800 x 2550
1940 x 800 x 2550
1940 x 800 x 2550
1940 x 800 x 2550
Weight - Machine
(2) kg 635
659
686
704
Construction - Material / Colour
Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey (RAL 7035)
Cooling Coil
Copper Tube/Turbulated Coated Aluminium Fins
Coating Plain
Plain
Plain
Hydrophilic
Cooling/Dehum Stages 1 (Modulated)/1
Fan & Motor
(3) Centrifugal - Designed to 50Pa ESP
Motor / Filter Type Belt / Standard
Belt / Standard
Belt / Standard
Belt / Standard
Quantity / Motor Size kW 2 x 3.0
2 x 4.0
2 x 5.5
2 x 5.5
Speed @ 50Pa ESP rpm 945
1089
1216
1216
Maximum ESP Pa 275
205
145
145
Speed @ Maximum ESP rpm 1142
1209
1284
1284
Nominal Airflow m³/s 5.0
5.8
6.5
6.5
Connections
Inlet/Outlet mm 54
54
54
54
Condensate Drain Hose mm 19
19
19
19
Filtration
Disposable to BS EN 779 - G4 - 97mm
Quantity 6
6
6
6
OPTIONAL EXTRAS
Electric Heating
kW 22.5
30.0
30.0
30.0
Humidifier
kg/hr 3.0 - 15.0
3.0 - 15.0
3.0 - 15.0
3.0 - 15.0
Feed/Drain 3/4” BSPF Braided flexible hose/19mm hose connection
HE & Pre Filters
Disposable to BS EN 779 - F6 - 97mm + Disposable to BS EN 779 - G3 - 22mm
Quantity 6 + 6
6 + 6
N/A
N/A
HE & Pre Filter Motor Selection
Motor / Filter Type
Belt / HE
Belt / HE
N/A
N/A
Quantity / Motor Size
kW 2 x 3.00
2 x 5.50
N/A
N/A
Speed @ 25Pa ESP rpm 1105
1231
N/A
N/A
Maximum ESP Pa 95
120
N/A
N/A
Speed @ Maximum ESP rpm 1143
1284
N/A
N/A
Fan Gain kW 2 x 1.76
2 x 3.24
N/A
N/A
Larger Fan Motor Size
(3)
Motor / Filter Type Belt / Standard
Belt / Standard
N/A
N/A
Quantity / Motor Size kW 2 x 4.00
2 x 5.50
N/A
N/A
Maximum ESP Pa 450
300
N/A
N/A
Speed @ Maximum ESP rpm 1283
1280
N/A
N/A
Fan Gain kW 2 x 2.35
2 x 3.24
N/A
N/A
Next Larger Fan Motor Size
(3)
Motor / Filter Type N/A
N/A
N/A
N/A
Quantity / Motor Size kW N/A
N/A
N/A
N/A
Maximum ESP Pa N/A
N/A
N/A
N/A
Speed @ Maximum ESP rpm N/A
N/A
N/A
N/A
Fan Gain kW N/A
N/A
N/A
N/A
Condensate Pump
Head m 10.8
10.8
10.8
10.8
Flow l/m 5
5
5
5
Drain 10mm S/Steel Stub Connection
Low Pressure Hot Water
Copper Coil/Aluminium Fin
Capacity Gross (4) kW 29
32
34
34
Water Flow (Nominal) l/s 0.63
0.69
0.74
0.74
LPHW Connection Sizes mm 22
22
22
22
Threaded Connections
Brass Male Taper in 2
2
2
2
(1) Entering air 24°C/45% RH ambient 35°C.
(2)
Refer to Dimensional & Installation Data Split case information.
(3) Based on standard front return air and grilles. HE & Pre filters may alter the motor selection, see Optional Extras or contact Airedale for details.
(4) Based upon low pressure hot water 82°C inlet/71°C outlet. Air on 20°C. Refer to Design Data - Chilled Water Models.
CHILLED WATER