Technical data
Precision Air Conditioning
-
V
Precision Air Conditioning
Technical Manual : 6258867 F 07/2012
29
General Specification - Air Cooled Models
MECHANICAL DATA
V19A
V23A
V25A
Single Circuit
V19X
V23X
V25X
A Model - Matched Condensing Unit CUS6
CUS7.5
CUS8.5
X Model - Matched Condenser C25
C35
C45
Capacity
Nom Cooling (Gross) - A (1) kW 16.6
20.0
25.2
Nom Cooling (Gross) - X (1) kW 18.5
21.8
26.9
Capacity Steps 1
1
1
Fan Gain kW 1 x 0.44
1 x 0.88
1 x 1.29
Dimensions - H x D x W
(2) mm 1940 x 800 x 1450
1940 x 800 x 1450
1940 x 800 x 1450
Weight - Machine - A
(2) kg 341
356
366
Weight - Machine - X
(2) kg 396
451
469
Construction - Material / Colour
Galvanised Sheet Steel, Epoxy Baked Powder Paint - Light Grey (RAL 7035)
Evaporator
Rifled Copper Tube/Turbulated Aluminium Fins
Coating Plain
Plain
Hydrophilic
Cooling/Dehum Stages 1/1
1/1
1/1
Fan & Motor
(3) Centrifugal - Designed to 50Pa ESP
Motor / Filter Type Direct / Standard
Belt / Standard
Belt / Standard
Quantity / Motor Size kW 1 x 0.74
1 x 1.5
1 x 2.2
Speed @ 50Pa ESP rpm N/A
790
872
Maximum ESP Pa 50
180
260
Speed @ Maximum ESP rpm N/A
932
1079
Nominal Airflow m³/s 1.50
1.9
2.1
Compressor - X
Single - Scroll / Polyol Ester Oil
Quantity 1
1
1
Oil Charge Volume (Total) l 1.65
3.25
3.80
Refrigeration
Single Circuit
Refrigeration Control Thermostatic Expansion Valve (Optional EEV)
Refrigeration Type (4) R407C (Optional R22)
Holding Charge Inert Gas
Connections
Liquid (Sweat) - A & X in 5/8
5/8
5/8
Suction (Sweat) - A in 7/8
1 1/8
1 1/8
Discharge (Sweat) - X in 3/4
3/4
7/8
Condensate Drain Hose mm 19
19
19
Filtration
Disposable to BS EN 779 - G4 - 97mm
Quantity 3
3
3
OPTIONAL EXTRAS
Electric Heating
kW 15.0
15.0
15.0
Humidifier
kg/hr 1.6 - 8.0
1.6 - 8.0
1.6 - 8.0
Feed/Drain 3/4” BSPF Braided flexible hose / 19mm hose connection
HE & Pre Filters
Disposable to BS EN 779 - F6 - 97mm + Disposable to BS EN 779 - G3 - 22mm
Quantity 3 + 3
3 + 3
3 + 3
HE & Pre Filter Motor Selection
Motor / Filter Type Belt / HE
Belt / HE
Belt / HE
Quantity / Motor Size kW 1 x 1.10
1 x 1.50
1 x 2.20
Speed @ 50Pa ESP rpm 575
898
997
Maximum ESP Pa 175
80
140
Speed @ Maximum ESP rpm 826
930
1082
Fan Gain kW 1 x 0.65
1 x 0.88
1 x 1.29
Larger Fan Motor Size
(3)
Motor / Filter Type Belt / Standard
Belt / Standard
Belt / Standard
Quantity / Motor Size kW 1 x 1.10
1 x 2.20
1 x 3.00
Maximum ESP Pa 205
395
475
Speed @ Maximum ESP rpm 865
1143
1265
Fan Gain kW 1 x 0.65
1 x 1.29
1 x1.76
Next Larger Fan Motor Size
(3)
Motor / Filter Type Belt / Standard
Belt / Standard
N/A
Quantity / Motor Size kW 1 x 1.50
1 x 3.00
N/A
Maximum ESP Pa 380
560
N/A
Speed @ Maximum ESP rpm 1022
1284
N/A
Fan Gain kW 1 x 0.88
1 x 1.76
N/A
Condensate Pump
Head m 10.8
10.8
10.8
Flow l/m 5
5
5
Drain 10mm S/Steel Stub Connection
Low Pressure Hot Water
Copper Tube/Aluminium Fin
Capacity Gross (5) kW 20
23
24
Water Flow (Nominal) l/s 0.43
0.50
0.52
LPHW Connection Sizes mm 22
22
22
(1) Entering air 24°C/45% RH ambient 35°C.
(2) Refer to Dimensional & Installation Data Split case information.
(3) Based on standard front return air and grilles. HE & Pre filters may alter the motor selection, see Optional Extras or contact Airedale for details.
(4) For refrigerant charges, refer to Design Data - Air Cooled Models.
(5) Based upon low pressure hot water 82°C inlet/71°C outlet. Air on 20°C. Refer to Design Data - Air Cooled Models.
AIR COOLED