Technical data

Precision Air Conditioning
-
V
Precision Air Conditioning
Technical Manual : 6258867 F 07/2012
27
Performance Data - Air Cooled Models
COOLING DUTIES
X Models
Cooling Capacity
(1)
Ambient
25°C 30°C 35°C 40°C Air On °C DB
/%RH
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
TC (kW)
SC (kW)
22 / 50 9.2
8.2
8.8
8.0
8.4
7.8
8.0
7.5
24 / 45 9.4
8.8
9.1
8.6
8.7
8.3
8.3
8.0
V9X / C11
26 / 40 9.8
9.4
9.4
9.1
9.0
8.8
8.6
8.5
22 / 50 11.5
10.5
11.0
10.2
10.5
9.9
10.1
9.6
24 / 45 12.0
11.4
11.5
11.1
11.0
10.6
10.4
10.2
V13X / C15
26 / 40 12.3
12.1
11.8
11.7
11.3
11.3
10.8
10.8
22 / 50 13.9
12.9
13.4
12.6
12.9
12.2
12.3
11.8
24 / 45 14.4
13.8
13.9
13.5
13.4
13.0
12.8
12.6
V16X / C20
26 / 40 15.0
14.7
14.4
14.3
13.9
13.8
13.3
13.3
22 / 50 19.5
15.1
18.8
14.8
18.1
14.5
17.3
14.2
24 / 45 20.1
16.5
19.3
16.2
18.5
15.9
17.8
15.5
V19X / C25
26 / 40 20.6
18.0
19.9
17.7
19.1
17.2
18.4
16.9
22 / 50 22.6
21.1
21.8
20.5
21.0
20.0
20.1
19.3
24 / 45 23.5
22.7
22.7
22.0
21.8
21.4
21.0
20.7
V23X / C35
26 / 40 24.4
24.0
23.6
23.4
22.7
22.6
21.8
21.8
22 / 50 27.8
24.9
26.9
24.4
26.0
23.9
25.0
23.3
24 / 45 28.8
27.0
27.9
26.4
26.9
25.7
25.9
25.0
V25X / C45
26 / 40 29.9
28.9
28.9
28.2
28.0
27.4
27.0
26.6
22 / 50 21.8
20.7
20.9
20.1
19.9
19.4
19.0
18.6
24 / 45 22.6
22.1
21.7
21.4
20.7
20.6
19.8
19.8
V23XD / C15 x 2
26 / 40 23.5
23.4
22.5
22.6
21.6
21.6
20.6
20.6
22 / 50 26.1
25.2
25.2
24.4
24.2
23.6
23.2
22.8
24 / 45 27.4
26.9
26.4
26.1
25.4
25.2
24.4
24.3
V31XD / C20 x 2
26 / 40 28.6
28.6
27.7
27.7
26.7
26.7
25.7
25.7
22 / 50 29.4
28.2
28.3
27.4
27.3
26.5
26.1
25.6
24 / 45 30.8
30.2
29.7
29.2
28.6
28.3
27.4
27.2
V35XD / C25 x 2
26 / 40 31.9
31.9
31.0
31.0
30.0
30.0
29.0
29.0
22 / 50 41.8
38.3
39.2
36.4
36.7
34.5
34.2
32.6
24 / 45 43.3
41.4
40.7
39.2
38.1
37.1
35.6
34.9
V41XD / C25 x 2
26 / 40 44.8
43.8
42.1
41.5
39.5
39.2
37.0
36.9
22 / 50 44.2
40.7
41.7
38.8
39.2
36.9
36.7
34.9
24 / 45 46.0
43.9
43.4
41.7
40.8
39.5
38.2
37.3
V45XD / C35 x 2
26 / 40 47.7
46.7
45.1
44.3
42.4
41.8
39.8
39.5
22 / 50 44.4
42.1
41.7
39.9
39.1
37.7
36.6
35.6
24 / 45 46.3
45.1
43.7
42.7
41.0
40.4
38.4
38.1
V50XD / C35 x 2
26 / 40 48.2
48.2
45.5
45.5
42.8
42.8
40.3
40.3
22 / 50 52.5
48.6
49.6
46.4
46.8
44.2
44.0
42.0
24 / 45 54.9
52.7
52.0
50.2
49.1
47.7
46.2
45.1
V55XD / C45 x 2
26 / 40 57.1
56.1
54.2
53.5
51.3
51.0
48.3
48.3
22 / 50 58.6
55.6
55.0
52.6
51.5
49.8
47.8
46.8
24 / 45 60.9
59.6
57.1
56.4
53.5
53.2
49.7
49.7
V65XD / C45 x 2
26 / 40 63.2
63.2
59.5
59.5
55.8
55.8
52.1
52.1
22 / 50 72.9
68.2
68.6
64.9
64.4
61.5
59.5
57.4
24 / 45 75.5
73.0
71.2
69.2
66.9
65.6
61.8
61.3
V80XD / C45 x 2
26 / 40 78.6
77.8
74.2
73.8
69.8
69.7
64.5
64.5
22 / 50 89.2
80.8
84.0
77.0
78.7
73.3
73.6
69.5
24 / 45 92.4
87.4
86.9
83.1
81.5
78.6
76.2
74.2
V90XD / CS50 x 2
26 / 40 95.5
93.1
90.0
88.3
84.5
83.5
79.0
78.6
TC = Total Cooling SC = Sensible Cooling
(1) Deduct fan motor gain for nett duties, refer to General Specification - Air Cooled Models.
OPERATING LIMITS
Cooling
Indoor Air Temperature +18°C to +26°C
Indoor RH% +40% to +50%
Outdoor Temperature -20°C to +4C
AIR COOLED