Technical data
Precision Air Conditioning
-
V
Precision Air Conditioning
Technical Manual : 6258867 F 07/2012
19
Controls
STANDARD FEATURES
User Friendly Display
Keypad
The default screen shows the unit status and room condition (°C/RH %) without the need
for interrogation and an easy to navigate menu structure for further interrogation
and adjustment.
Password Protection
The control system integrity can be maintained by restricting access with a password
PIN number.
CAUTION
IMPORTANT: To change the PIN number; please contact Airedale at time of order
with the preferred 4 digit number.
Remote On/Off
Terminals for interlocking are provided to enable or disable the unit remotely.
Fire Shut Down
Terminals for interlocking are provided to shut down the unit in the event of fire.
Compressor Anti-Cycle
Control
Programmed to provide automatic anti-cycling delays of up to 10 starts per hour with a
minimum off time of 3 minutes.
Compressor Rotation
On dual and triple circuit units the controller is programmed to provide automatic
compressor rotation to ensure equal compressor running times. In the event of a
compressor fault the controller is programmed to automatically select the next
compressor in order of running hours.
Compressor Hours Run
Log & Reset
Allows the user to monitor the running times of each compressor and reset
after maintenance.
Evaporator Fan Hours
Run Log & Reset
Allows the user to monitor the running times of the evaporator fans and reset
after maintenance.
Networking
A Local Area Network ( ) can be used to connect upto 6 units to offer
intercommunication and Duty/Standby control. This also allows the connection of
computers, printers and modems on the same communications ring. For further details,
please contact Airedale Controls.
CAUTION
When adding to an existing network, please consult Airedale to ensure
strategy compatibility.
GENERAL