General Description
OPTIONAL EXTRAS - GENERAL
Fan & Motor Anti
Vibration Mounts
Spring type vibration isolators can be fitted between the fan and motor mounting plate
and the unit chassis.
Condensate Pump
The condensate pump has a 6 litre reservoir with a capacity of 5 l/m at a head of 10.8m
and is mounted in the unit base, for pump performance; refer to Design Features &
Information.
On units with optional base return air, the condensate pump is supplied loose and must
be mounted in the floor void beneath the service connections.
Water Detector
2 methods are available:
1 A solid state (probe) sensor is supplied loose for remote mounting on site.
2 Tape suitable for sensing water droplets is supplied loose for remote mounting on
site. Standard tape length 10m.
Firestat
Installed in the return air stream to shut down the unit in the event of an unusually high
return air temperature.
Smoke Detector
Supplied loose for remote mounting to shut down the unit and activate the alarm upon
sensing the presence of smoke.
Take Apart Structure
If required, units can be supplied in 2 pieces for sites where access is restricted, the
overall height of the unit increases to 2040mm, refer to Dimensional & Installation Data in
this section.
Return Air Configuration
Standard unit configuration is front return air, the following options are available, please
specify at order:
A, X & CW Models
(Sizes 9 - 95)
Rear return air.
A & CW Models
(Sizes 19 - 95)
Base return air.
Open & Enclosed
Floorstand
Open or enclosed floorstands are available, complete with adjustable feet and floor tile
lip. The height of the floor stand can be specified at the time of order.