Installation manual

6
Connection block
at air conditioner
Rigid cable minimum area
1.5 mm
2
minimum 7 strand
15 Amp 2 pole RCD
Minumum contact
gap of 3mm in OFF
position
15 Amp
power inlet
Brown
Y & G
Blue
N A
4. Position Sparrow on roof
Remove the air conditioner from the carton and move
to installation position.
Put a circle of sealant around each bolt hole in the
weather collar.
Position the unit over the weather collar. The unit will
engage with the collar and self-align (Fig 6).
The unit weights approximately 28kg. Ensure a two
person lift or use a mechanical hoist to avoid the risk of
injury.
DO NOT slide the unit on the roof, this may damage
the weather collar and result in leaks.
Four M8 mounting holes on the chassis underneath
the air conditioner will line up with the corresponding
holes on the weather collar.
Fig 6: Apply sealant around bolt holes and then position unit
over the weather collar and set down gently.
5. Connect Electrical Supply
This unit MUST be installed in accordance with SAA
Wiring regulations and in particular AS3001 – 2008.
Refer Fig 7 for position of terminal block.
Connect electrical supply to terminal strip. Note
position of active, neutral and ground wires (Fig 8).
WARNING
This work should only be performed by a licenced
electrical tradesperson. Ensure that power is properly
disconnected at the supply (mains and/or battery).
When connecting wires into terminal strip apply suitable
clamping pressure to ensure wire is secure while taking
care not to over tighten and damage the exposed wire
ends.
Fig 7: Highlights the position of the terminal strip underneath
the unit.
Fig 8: Wiring diagram of power connection
from external supply to air conditioner.
Apply circle of
sealant around
4 bolt holes.