6. ASSESS ROOF THICKNESS
- Measure the roof thickness and
consult the table across to check
if adjustments to the duct length
are required.
- NOTE if the duct length needs
to be adjusted then cut the
excess from the un-notched end.
Roof thickness
(mm)
Comment
Duct length (mm)
Bolt length
25
Absolute minimum ring must be
removed from top of plenum ducting.
60
Standard
30
Use plenum duct as provided
65
Standard
40
75
Standard
50
85
Standard
60
95
Standard
85
120
Limit of std bolt
115
Absolute maximum
150
Installer to provide
General rule
Roof less than 30mm remove duct
ring. 30mm or thicker leave duct as
supplied
Duct length = Roof
thickness + 35mm
Roof greater than 85mm
thick will require installer
to provide longer bolts
7. ASSEMBLE DUCT
- Thread a hold down bar onto
the M8 bolt and push the bolt
almost all the way into the hole
in each corner of the brace
(Fig 9)
- Leave a 10mm gap between the
hold down bar and the recess in
the plastic brace. This will allow
for easier engagement with the
four corresponding threaded
holes in the unit.
- Turn the assembly over and add
the black plastic duct work to the
top of the assembly with the
notch upwards (Fig 10). The
notch is shown circled below.
- Align the notch with the inside
fans power cable.
When attaching the
duct to the unit take
care to ensure it forms
a tight, unbroken seal that
doesn’t allow cold air to escape.
Fig 9: Insert the four M8 bolts and hold down bars into the corners of the brace
Fig 10: Fit the black plastic duct onto the brace assembly ensuring a tight, sealed fit