IBIS Mk II Installation Instruction
6/8/2010 Page 5 of 9
3. Connect Electrical supply to unit
1. This unit MUST be installed in accordance with National Wiring regulations and in particular AS3001 - 2008
2. Refer to wiring diagram below. Connect electrical supply to terminal strip. Note position of active, line and ground
4. Assess roof thickness and modify flexible duct and hold-down bolts if required
Measure the thickness of the caravan roof and use following table to check if adjustment to hold down bolts and duct length is required:
Roof thickness (mm)
Include ‘H’ frame if used
Duct length required
(mm)
Hold down bolt length
required (mm)
125 150 (as supplied) As supplied
100 125 (cut 25) As supplied
80 105 (cut 45) As supplied
60 85 (cut 65) Cut 50
40 65 (cut 85) Cut 70
25 (absolute minimum) 50 (cut 100) Cut 85
NOTE - If the Duct length needs to be adjusted then cut excess from the un-notched end
connection block at airconditioner
Brown
Blue
AN
Y & G
Rigid cable min. area 1.5 squ. mm
min 7 strand
15 Amp 2 pole RCD
Minimum contact gap of 3mm
in OFF position
15 Amp power inlet