Specifications
HighInletTemperatureRefrigeratedAirDryer
23
Problem Probable Cause Remedy
HighRefrigerationCircuit
HeadPressure
(compressor is overloaded
and gauge is reading out
of recommended pressure
range).
Refrigerationcondenser
coil fouled or dirty or air
flow blocked.
Clean / blow off condensing coil of dirt or
debris from the inside out. Clear area in front of
condensing coil of any items blocking airflow to
coil.
Condenser fan motor not
working properly or faulty.
Check fan motor for proper voltage and amp
draw, repair or replace fan motor.
Defectivefancontrol
switch.
Repairswitchorreplace.
Ambient temperature
too high at refrigeration
dryer location.
Cool ambient temperature around location of
refrigerationdryerdowntoamaximumof100°
F or relocate dryer to a different area with lower
ambient temperature.
Compressed air
temperature entering the
refrigeration dryer is
too high.
Check compressed air inlet temperature to ensure
it is within the operating parameters listed in the
DesignParametersection.Checkaircompressor
after cooler for malfunction.
Faultyheatexchanger,
compressed air leaking
into refrigeration circuit.
Repairorreplaceevaporatororheatexchanger
and recharge with refrigerant.
LowRefrigeration
CircuitHeadPressure
(gauge is reading out of
recommended
pressure range).
Ambient temperature
too low at refrigeration
dryer location.
Increase ambient temperature at refrigeration
dryer location or relocate dryer.
Refrigerationdryer
circuit low on refrigerant.
Refrigerationcircuitlowonrefrigerant,locate
leak in refrigeration circuit, repair and recharge
according to specifications.
Refrigerationcompressor
not working properly or
faulty.
Check refrigeration compressor for proper
voltage and amp draw, repair or replace
refrigeration compressor.