Specifications
25
Non-CyclingRefrigeratedAirDryer
Problem Probable Cause Remedy
High refrigerant suction
pressure, suction gauge
reading out of range and
water downstream of
refrigeration dryer.
Refrigerationcircuit
hot gas bypass valve out of
adjustment or defective.
Contact technical support for assistance.
Refrigerationexpansion
valve or TXV adjustment
fitting out of adjustment.
Contact technical support for assistance.
Low refrigerant suction
pressure, suction gauge
reading out of range and/
or refrigeration compressor
covered with ice.
Refrigerationcircuithot
gas bypass valve out of
adjustment or defective.
Contact technical support for assistance.
Refrigerationexpansion
valve or TXV adjustment
fitting out of adjustment
and is not feeding enough
refrigerant to the evaporator.
Contact technical support for assistance.
Excessivepressuredrop
on the high side of the
refrigeration circuit.
Checkforapluggedinlinefilterdryerorreceiver
on the refrigeration circuit that could be causing
these restrictions.
Compressor oil
downstream of
refrigerated air dryer.
Checkoptionalprefilter
condensate drain for
failure.
Dismantleprefilterdrainandcleanorreplace.
Failedorplugged
prefilter element.
Checkoptionalprefilterandreplaceelement.
Air compressor injecting
excessiveoilintothe
airstream.
Checkaircompressorforoilleakintotheair
stream,checkairoilseparatorelementfor
failure.