Specifications
Troubleshooting Table
Non-CyclingRefrigeratedAirDryer
Problem Probable Cause Remedy
Water downstream
of dryer system or no
discharge from separator/
filter.
Failedorshortcircuited
timer on drain.
Replacetimerdrain.
Faileddrainsolenoid. Replacetimerdrain.
Bulkliquidenteringthe
dryer from upstream.
Checkdrainsonaftercooleroraircompressor.
Inletcompressedair
temperature to dryer
exceedsdryercapacityair.
Checkinletairtemperatureandadjustas
required to meet specifications.
InletcompressedairCFM
flowrateexceedsdryer
capacity.
Checkininletaircfmflowrateandadjustas
required to meet specifications.
Leakintheairtoair
sideoftheheatexchanger.
Replaceheatexchanger.
Water downstream and
dryersystemnotworking
properly.
Refrigerationcompressor
stopped due to plugged or
dirty condenser coil.
(HighPressure)
Clean condensing coil and ensure adequate
ventilation of unit.
Refrigerationcompressor
cycles on/off and cannot
maintain suction pressure.
Checkcondensingcoilfordirtordebristhat
could prohibit adequate ventilation of the
refrigerantcircuit.Ifitisclean,checkrefrigerant
pressure gauge(s) to determine if the unit is low
on refrigerant.
Low refrigerant. Checkforleakinrefrigerationcircuit,repairand
recharge according to specifications.
Low refrigerant, possible
leakinairtorefrigerant
sideofheatexchanger.
Repairorreplaceheatexchangerandrecharge
according to specifications.
Refrigerationcompressor
is overheated.
Turnoffdryerandwait20-40minutes,restart
dryer.Refrigerantcontrolsettingsmayneed
adjustment, contact technical support.
Refrigerationcompressor
has burned out or
windings have gone
to ground.
Replacecompressor,checkforleakin
refrigeration circuit, repair and recharge
according to specifications, contact technical
support.
21