Specifications

29
HeatlessRegenerativeDesiccantAirDryer
Aircel Programmable Controller
Step 5: Vessel 1 Depressurizing (0-5 secs)
Vessel1(T1)purgeexhaustpilotsolenoidvalveisenergized
whichsuppliescontrolairtothepurgeexhaustvalve(V3)which
opensslowly,depressurizingvessel1(T1).Simultaneouslythe
inletvalvesV2andV1shiftpositionswithapneumaticsignal
fromvessel1(T1)purgeexhaustpilotsolenoidvalvetotheinlet
tower selector pneumatic pilot valve which in-turn supplies a
pneumaticsignaltotheinletvalvestoopenvalve(V2)andclosevalve(V1),directingtheinletair
tovessel2(T2)tobedryingtheair.Theairflowsupthroughthedesiccantbedandexitstothe
outletvalve(V6)totheoutletparticulatefilterthentothecustomerdryprocessairsystem.
Step 6: Vessel 1 Regenerating (6-240 secs)
Step6isacontinuationofstep5exceptvessel1(T1)willbe
regenerating,vessel1(T1)purgeexhaustvalve(V3)isstillopen,
vessel2(T2)isdryingtheinletair.Asmallportionofdryoutlet
airfromvessel2(15%averagebasedonstandarddesigncapacity
of100psig,100°Finletair,100°FambientairandPDPof-40°F)
istakenthroughasmallorificeintheoutletlineandusedto
regeneratethedesiccantbedinvessel1(T1)until240seconds
has been reached.
Step 7: Vessel 1 Repressurizing (241-300 secs)
Vessel1(T1)purgeexhaustpilotsolenoidvalvewillde-energize
causingvessel1(T1)purgeexhaustvalve(V3)toclose,this
allowsvessel1(T1)torepressurizetolinepressure,sinceair
continues flowing though the small outlet orifice pressurizing
vessel1(T1).Theinlettowerselectorpneumaticpilotvalve'
maintainstheinletvalve(V2andV1)positions.
Step 8: Extended Drying Vessel 2
AfewsecondsbeforetheendofrepressurizationtheAHLD
E-SERIESController’sintegratedEnergyManagementPurge
ReductionSystemlooksatthemoisturesensor,ifthemoisture
loadislowenough,vessel2(T2)willcontinuetodryforan
extendeddryingperioduntilthemoistureloadhasreacheda
sethighlevel,thecontrollerwillthenadvancetostep1andthe
vessels will switch. This feature reduces the overall purge
consumptionsavingenergyandmoney.Theextendeddrying
cycletimerwillcountto30minutesunlesstheEMSrelativehumiditysensorishigherthanthe
setpoint.After30minutes,theunitwillswitchandcontinuenormaloperationuntilthenext
extendedsavingsstep.AtthestartofeachextendedsavingsstepthePLCchecksforfaults,EMS
relativehumiditysensorvalueandhighoutletdewpointsetting(optional)toensureifthedryer
needstocontinuedryingandthedryerwillgointoextendeddrying.Ifthedryerneedstocontinue
tothenextsteptoregenerate,theextendedsavingsstep4willbeskipped.