Instruction manual
Gap to be kept to a 
minimum 
3m minimum 
Bottom of air 
curtain to be  
level with top of 
door opening 
4. Installation Details. 
Health and Safety 
Due account should  be taken of any obligations 
arising  from  the  Health and  Safety  at Work Act 
1974  or  relevant  codes  of  practice.  In  addition 
the  installation  must  be  carried  out  in 
accordance with the current IEE wiring        reg-
ulations and any other relevant British Stand-
ards and Codes of Practice by a qualified install-
er. Isolate all electrical supplies  to  the  heater  & 
control panel before proceeding. 
For  your  own  safety  we  recommend the  use  of 
personal  protective  equipment  when  handling 
this air curtain. 
Airbloc  air  curtains  are  supplied  with  mounting 
brackets  pre-fitted,  and  can  be  mounted  either 
as single  units, or in  multiples, which  can be 
bolted together to suit various door widths. 
The minimum mounting height is 3 metres (See 
diagram 2 below). 
4.1 
Each  single  air  curtain  should  be  supported  by 
cantilever  brackets  (not  supplied)  then  fixed 
back to the building structure by bolting directly 
using  suitable  support  brackets,  or  by  
suspending  from  above  using  suitable 
steelwork. (See diagram 3, page 6). 
4.2 
Multiple  air  curtains  should  be  bolted  together 
using 3 off M10 set pins, nuts and washers fitted 
through  the  holes  provided  in  the  mounting 
brackets, then suitable support channels (not 
supplied)  must  be    fixed  on  top  of  the  factory 
fitted  brackets  along  the  full  length  of  the 
assembled air curtains to spread the load.  
The assembly can now  be fixed back to  the 
building  structure  by  bolting  directly  using  
suitable support brackets,  or suspending from 
above using steelwork. (See diagram 4 page 6). 
If  required,  the  support  channel  may  be 
extended  slightly  past  the  ends  of  the  air 
curtains to aid fixing. 
 Note: Where multiple air curtains are fitted  
 above  up  and  over  doors  or  where  
central  support  is  inappropriate,  the  support 
channel should be replaced with channels of  a 
greater  cross  section  to  prevent  the  assembly 
from bending. 
4.3 Mounting. 
It may be necessary to adjust the position of the 
air  outlet  louvres  to  provide  the  correct  airflow 
across  the  door  opening.  This  can  be  done  by 
first loosening the four locking pins   located two 
at  each end  of the louvres  (arrowed, Fig.  A), 
then  loosening  the  intermediate  locking  Allen 
pins (arrowed, Fig. B). The louvres can now be 
moved  to  the  desired  position  and  the  locking 
pins re-tightened. 
 Note:  The  AB  225  model  has  two  pairs  of 
intermediate locking Allen pins, whereas the 
AB 175 model only has one pair. 
Fig. A 
Locking pins 
Diagram 2. 
Locking Allen pins 
Fig. B 