Instruction manual

3. Technical Specification.
ACT03-1 ACT04-1 ACT06-1
General Data
Recommended height M 2.5 3.0
Min/max height M 2.2-3.0 2.5-3.5
Heat medium Electric heated
Maximum heat capacity kW 3.0 4.5 6.0
Heat setting 3
Heat setting kW 1.0/2.0/3.0 1.5/3.0/4.5 2.0/4.0/6.0
Fan type Crossflow
Fan dia mm 60
Fan settings 1
Air outlet Fixed vent
Switching type Remote switchbox
Weight Recessed / Surface Mounted kg 7 / 10 10 / 16
Electrical Data
Maximum heat capacity kW 3.0 4.5 6.0
Supply voltage 230V 1ph 50Hz
Total load amps 13 20 27
Cable size 2 x 2.5mm² + E 2 x 4.0mm² + E
External fuse size amps amps 16 25 32
Switch box wiring 2 x 2.5mm² + E 2 x 4.0mm² + E
Mains terminal block position Inside cover
Control terminal block position Inside cover
Air Data
Fan setting 1
Airflow l/s 50 60 120
Noise level dBA 44 52
Dims Data
Length mm nom 600
Depth mm nom 600
Total Height (incl terminal box) mm 175 (187 Surface Mounted)
4. Electrical Connections.
These units are suitable for connection to
230/240V 50Hz supplies. Maximum cable inlet
size is 4mm².
The appliance shall be connected to the supply
via an appropriate switched fused double pole
isolator having a contact separation of greater
than 3mm.
The ACT-1 is supplied with a remote control box
which houses 3 rocker switches.
The mains supply can be fed either directly to the
heater or the remote control box as per the
following diagrams.
For thermostatic control a room thermostat of
appropriate switch rating maybe connected to the
circuit. The thermostat should be wired between
the isolator switch and the heater remote switch.