Instruction manual
3. Technical Specification. 
ACT03-1  ACT04-1  ACT06-1 
General Data 
Recommended height  M  2.5   3.0 
Min/max height  M  2.2-3.0   2.5-3.5 
Heat medium     Electric heated 
Maximum heat capacity  kW  3.0  4.5  6.0 
Heat setting     3 
Heat setting  kW  1.0/2.0/3.0  1.5/3.0/4.5  2.0/4.0/6.0 
Fan type     Crossflow 
Fan dia  mm  60 
Fan settings     1 
Air outlet     Fixed vent 
Switching type     Remote switchbox 
Weight Recessed / Surface Mounted  kg  7 / 10   10 / 16 
Electrical Data 
Maximum heat capacity  kW  3.0  4.5  6.0 
Supply voltage     230V 1ph 50Hz 
Total load  amps  13  20  27 
Cable size     2 x 2.5mm² + E  2 x 4.0mm² + E  
External fuse size amps  amps  16  25  32 
Switch box wiring     2 x 2.5mm² + E  2 x 4.0mm² + E  
Mains terminal block position     Inside cover 
Control terminal block position     Inside cover 
Air Data 
Fan setting     1 
Airflow  l/s  50  60  120 
Noise level  dBA  44  52 
Dims Data 
Length  mm  nom 600 
Depth  mm  nom 600 
Total Height (incl terminal box)  mm  175 (187 Surface Mounted) 
4. Electrical Connections. 
These  units  are  suitable  for  connection  to 
230/240V  50Hz  supplies.  Maximum  cable  inlet 
size is 4mm².  
The  appliance  shall  be  connected  to  the  supply 
via  an  appropriate  switched  fused  double  pole 
isolator  having  a  contact  separation  of  greater 
than 3mm. 
The  ACT-1  is supplied  with  a  remote  control  box 
which houses 3 rocker switches.  
The mains supply can be fed either directly to the 
heater  or  the  remote  control  box  as  per  the 
following diagrams. 
For  thermostatic  control  a  room  thermostat  of 
appropriate switch rating maybe connected to the 
circuit.  The  thermostat  should  be  wired  between 
the isolator switch and the heater remote switch.  