Instruction manual

1.4 Location
All units should be installed horizontally.
It is recommended that the recessed ceiling
heater is installed within the ceiling void or roof
space and the surface mount ceiling heater be
suspended from a solid fixing via four 10mm drop
rods.
Care must be taken to allow complete free air
movement into the inlet grilles of the unit to ensure
the correct working operation of the heater.
If the ACT03-1/04-1 heaters are mounted close to
the wall or corner, the discharge opening should
face the wall.
The minimum distance of 0.8m or 1.2m for the
ACT06-1.
1.5 Clearance distances
It is recommended that a minimum clearance of
50mm is allowed around the case and 30mm
above the heater.
The clearance allows for cable entry and prevents
combustible surfaces over-heating.
Minimum mounting height (floor to grille) is:
2.2m - ACT03-1/ACT04-1
2.5m - ACT06-1.
The recommended mounting height is:
2.5m - ACT03-1/ACT04-1
3.0m - ACT06-1.
1.6 Standards
Units conform to the European electrical standard
BS EN 60335-2-30
All must be wired in accordance with I.E.E
regulations for the Electrical Equipment of
Buildings.
1.7 Health and Safety
Sole liability rests with the installer to ensure that
all site safety procedures are adhered to during
installation.
Sole liability rests with the installer to ensure that
protective safety wear such as hand, eye, ear and
head protection is used during installation of the
product.
Do not rest anything especially ladders against the
product.
WARNING:
THIS HEATER SHOULD NOT BE
INSTALLED WHERE THERE IS A
CORROSIVE ATMOSPHERE.