Instruction manual
1.4 Location 
All units should be installed horizontally.  
It  is  recommended  that  the  recessed  ceiling 
heater  is  installed  within  the  ceiling  void  or  roof 
space and the surface mount ceiling heater be 
suspended from a solid fixing via four 10mm drop 
rods. 
Care must be taken to  allow complete free  air 
movement into the inlet grilles of the unit to ensure 
the correct working operation of the heater.  
If the ACT03-1/04-1 heaters are mounted close to 
the  wall  or  corner,  the  discharge  opening  should 
face the wall.  
The  minimum distance  of 0.8m  or  1.2m  for  the 
ACT06-1. 
1.5 Clearance distances 
It  is  recommended  that  a  minimum  clearance  of 
50mm  is  allowed  around  the  case  and  30mm 
above the heater.  
The clearance allows for cable entry and prevents 
combustible surfaces over-heating.  
Minimum mounting height (floor to grille) is: 
2.2m - ACT03-1/ACT04-1  
2.5m - ACT06-1.  
The recommended mounting height is:  
2.5m - ACT03-1/ACT04-1  
3.0m - ACT06-1. 
1.6 Standards 
Units conform to the European electrical standard 
BS EN 60335-2-30  
All  must  be  wired  in  accordance  with  I.E.E 
regulations  for  the  Electrical  Equipment  of 
Buildings. 
1.7 Health and Safety 
Sole liability rests  with the  installer to ensure  that 
all  site  safety  procedures  are  adhered  to  during 
installation. 
Sole liability rests  with the  installer to ensure  that 
protective safety wear such as hand, eye, ear and 
head  protection  is  used  during  installation  of  the 
product. 
Do not rest anything especially ladders against the 
product. 
WARNING: 
THIS HEATER SHOULD NOT BE 
INSTALLED WHERE THERE IS A 
CORROSIVE ATMOSPHERE. 










