6.1 Control
The remote control box houses 2 switches, a
double pole and a single pole, and gives the
following functions:
Switch ’FAN’ on = Off/Fan Only
Switch ’I’ on = ⅓ Heat
Switch ’II’ on = ⅔ Heat
To switch on the appliance and operate the blower
in Ambient mode, depress the left-hand switch
(marked “FAN”).
When the centre switch only (marked ‘I’) is
depressed the heat output is of full heat.
ACT03-1 = 1.0kW, ACT04-1 = 1.5kW, ACT06-1 =
2.0kW.
When the right hand switch only (marked ‘II’) is
depressed the heat output is of full heat.
ACT03-1 = 2.0kW, ACT04-1 = 3.0kW, ACT06-1 =
4.0kW.
When both the centre switch and the right-hand
switch are depressed the full heat output is
available. ACT03-1 = 3.0kW, ACT04-1 = 4.5kW,
ACT06-1 = 6.0kW
6.2 Protection
The unit is protected in the event of fan failure, or
an obstruction of the free air flow, by a thermal
PTC Self Hold Cut Out.
Having tripped the PTC Cut Out remains open,
effectively switching off the heating elements, as
long as mains power is available inside the
appliance.
The PTC Cut Out will only reset when the
appliance is switched OFF and allowed to cool for
at least 20 minutes.
6.3 To reset the PTC Self Hold Cut Out
a) The cut-out is reset by switching OFF mains
power to the appliance.
b) Allow the appliance to cool for 20 minutes.
Re-start, switch ON the appliance. If the Cut-out
trips again, a qualified electrician should be
consulted.