@ OWNER AND TEGHNICAL MANUAL SMOKEMASTER' MODEL C-12 SELF-CONT\INED ELEOTRONIC AIRCLEANER
TABLEOF CONTENTS SECTION PAGE OWNERM S A N U A LP A R TI INTRODUCTION 2 COMPONENTS 3 PRINCIPLES OF OPERATION. . 3 OPERATING INSTRUCTIONS. 4 MAINTENANCE 4 T E C H N I C AMLA N U A LP A R TI I SPECTFTCATTONS G E N E R AILN F O R M A T I O N Application ......6 ....6 .......6 OutdoorAir... .........7 Sizing. ....7 INSTALLATION .......8 Location .........8 C e i l i nMgo u n t i n g ........9 W a lMl o u n t i n g . . . . ......9 Wiring. ....9 CHECKOUT ....10 SERVICE .......
OWNER MANUAL SMOKEMASTER FART1 Your Smokemaster Electronic Air Cleaner is an advanced sel{-contained electronic air cleaner. The Model C-I2 is an e{ficient indoor pollution lighter while reducing costly energy consumption. CLEANAIR A clean lresh atmosphere is a plus to any business. With yqur new Smokemaster Electronic Air Cleaner, your customers and employees can now breathe air that is relatively lree ol smoke, dust or pollen.
COMPONENTS OF THE C.l2 COMPONENTS AIR CLEANER ELECTRONIC Cabinet& Grllle Iow prolile design and finish options assure decor compatibility while also made oI durable steel. Intake grille adds to the compatible appearance. RemovablePrefilters Metal mesh prelilters catch larger particles belore entering the electronic cells. System Indicator Lamp, Power Pack and Three Speed Control The System Lamp monitors the electrical output automatically indicating any system mallunciion.
OPERATING INSTRUCTIONS FAN SWITCH Your electronic air cleaner has an OII-low-Med-Hi switch. The electronic air cleaner and built-in Ian are designed to run simultaneously. Turn OII the air cleaner belore opening the access door to remove the electronic cells lor cleaning. SYSTEMLIGHT Your electronic air cleaner is equipped to tell you simply and quickly that it is working properly. The amber system light tells at a glance the status ol the power supply. The system light should be on when the unit is on.
TEGHNICAL MANUAL SMOKEMASTER FART2 5 THE C-12 IS A SELF-CONTAINEDELECTRONIC AIR CLEANER FOR USE IN COMMERCIAL AND LIGHT INDUSTRIAL APPLICATIONS. THE AIR CLEANER IS MOUNTED IN THE ROOM OR AREA WHERE THE AIR IS TO BE CLEANED. A. THREE.SPEED FAN CIRCULATES AIR THROUGH A METAL MESH PREFILTER AND AN ELECTRONIC CELL. IT RE' MOVES AIRBORNE PARTICLESSUCH AS DUST, SOOT, POLLEN, AND TOBACCO SMOKE FROM THE AIR. power supply output is not r Self-regulating affected by moderate fluctuations in line voltage.
SPECIFICATIONS MODEL: C-l 2 includes 2 electronic cells and a S-speed fan. Dischargesair in four directions parallel to ceiling upon which it is mounted. WEIGHT: 79 lbs. [36 kg] shipping, 69 lbs. [3] kg] installed,including electronic cells.Each cell weighs il / 2 l b s . I a . 3k e ] . POWER CORD: lO Ieet (3 meters) long, 3 wires 3-prong plug included with lzOV 60 I-Iz models. On 22O|2NV,5O tlz models, plug must be purchased locally.
- Continued GENERALINFORMATION MAKE.UPAIR Recommendedquantitiesof clean outdoor ventilation air for variousapplicationsare described in Table 2 of the ASHME Standard 62-89'Ventilation for AcceptableIndoor Air Quality.' ASHRAE (AmericanSociety of Heating,Refrigerating,and Air ConditioningEngineers,Inc., Phone #404-63684OO)notes that these recommended outdoor air quantitiesmay be reduced by the use of clean, recirculatedair if the IAQ Procedure6.
INSTALLATION l. Installer must be a trained, experienced serviceman. 2. Disconnect power supply before installation to prevent electrical shock and eguipment damage. - L . *E* a -f* _T_ -T 3. All wiring must comply with applicablecodes and ordinances. t +l 4. Do not exceed the ratings given in the SPECIFICATIONSsection. c.rz f+ t' 5. Always conduct a thorough checkout when installationis complete. LOCATION The C 12 should be mounted on th€ Giling near the center of the room.
CEILING MOUNTING The C-I2 ir mounted by supending it from the csiling. The mounting holes in the C- I 2 ore spoced 16 inches (406.5 mm) between centers in both directions. This mqkes it eqsy to fosten the oir clecrner directly to the ceiling tomework with 8 inch log screws. Lecrve spqce tor the power cord to run between the top ol C-12 qnd ceiling. The power supply cord must not be concecrled crbove ceilings or behind wqlls. Notc in Fig.
PERMANENTWIRING To permanently wire the C-12 follow these instructions exactly. All wlring must comply with applicable codes and ordinances. Wire the C-12 using the built-in iunction box as indicated in lig.7 The power source must be l2O volt, 60 Hz. It is recommended that No. 14 or heavier wire be used to complete the wiring from the junction box to the external power source. However, be sure to comply with local codes. ii\ l. Open C-12 junction box cover (Fig.7). 2.
SERVICE The lollowing instructions are intended lor qualiIied service personnel only. Dangerotrs line voltage circuits are o
PROCEDURE MOTORMAINTENANCE The manufacturer of the motor used in the C-12 necommendsoiling of the motor at least once a year. The followingprocedurecan be followed: o De-energizethe unit. . Removethe prefilters and cells from the cabinet. . Removethe fan blade from the motor shaft.* . Unscrew the four screws holding the motor mounting plate, and lower the motor. THE WIRING NEEDNOT BE DISCONNECTED. r There are lwo oil holeson the motor: 1. Near the motorshaft. 2.
DIAGNOSTIC CHECKS DIAGNOSTICCHECKS 1. ENERGIZE ELECTRONICAIR CLEANER a. Be sure that the electronic cells and prefilter screensare clean, dry, and properly installed in the air cleaner. b. Energize the air cleaner and check for operation in all fan speeds.In each case the fan NO FAN OPERATION should run and the SYSTEM light shouldturn on. -If the fan does not run, check the fan motor, power sourc€,and interlock safety switch. -lf the SYSTEM light does not come on, go to step 3.
COMFONENT CHECKS SOURCE CHECKFANMOTORANDPOIVER lf the fan doesnot run whentheswitch is in HIGH,MEDIUMand LOWpositiom, checkvoltagesuppliedto the motor. I. If the morordoesnot turn with the correctvoltageapplied,checkto seethat the shaft is free to turn. Replacr the motor if necdsary. !o FAi orfnatroN I 2. If the correctline voltageis not m€asured, check beck throughtho wiring to the powsr source,including intcrlocksafetyswitches.
I 2 3 4 5 _q _ 7 8 I 10 11 PARTNUMBER 120V. 2201240V. 60 HZ MODELS 50 HZ MODELS 41009 (2) 4 1 0 0 9( 2 ) 38001 (2\ 38001 Q\ 4 6 1 1 3( 2 ) 4 6 1 1 3( 2 ) 07089 07071 10106 10106 DESCRIPTION NO. Prefilter ElectronicCell Contact Board Assembly PowerSupply Door InterlockSwitch 05013 37022 Fan _ Power Cord _7 Control Switch _I lndicator Light I 4rorl louo-loor? f- ,0016 a ,oor5 Intake Grille, lvory Intake Grille, Black TOLL FREE1-800-328-0787 PARTSNOTILLUSTRATED of 5),PartNo.
GUIDE SPECIFICATIONS MODELC.I2 Scope: The following describesa self-contained,cord-connected,electronic air cleaning device to be suspendedfrom the ceiling. Description: 1' Unit shall operate from ordinary 120 volt,50 Hz. power source, drawing no more than 3.3 amPeres. 2'.unit shall be equipp-edwith power cord and three prong plug and also equipped to be hard wired in installation if desired. 3' Provision for ground wire connectionin field wiring compartment shall be made.
CERTIFICATE OF WARRANTY WARRANW LIMITEDONEYEARSMOKEMASTER Air Quality Engin€ering, Inc. warrants the Smokemaster Electronic Air Cleaners to be free from delects in worloanship or materials, under normal use and service, Ior a period oI one ( I ) year ftom the date oI purchase by tbe congumer II, at any time during the warranty period, the product is de{ective or mallunctions, Air Quality Engineering, Inc. shall repair or replace it (at Air Quality Engineering's option) 1yifhin 6 reasonable period o{ time.