Technical data

5
8. Read Global Binary Broadcast from another Controller
9. Sensor #6 can be assigned to read Static Pressure
Each input is separately configured so combinations of any type of input on the same
controller are possible.
All readings can be overridden to specific values for test purposes. All thermister sensors
can also be calibrated by entering positive or negative offsets to be applied to the current
readings. All 4 – 20ma readings can be calibrated if the user has the exact current or
resistance values available for entering in the calibration fields.
Right-Click on the desired analog input reading to access the pop-up menu shown above
and then select the desired function. If you are calibrating or overriding the reading, the
following window will pop-up. Enter the desired calibration offset or specific reading
you wish to force the input to and press the Enter key. The window will automatically
close and send the command to the controller. If you select the Clear Sensor Override
option, a window will not appear but the clear command will be sent to the controller.
- OR -