Operating instructions
REQUIRED SEPARATELY PURCHASED PARTS FOR DRAINAGE
INSTALLATION:
•
5
/8”OD
1
/2” ID DRAIN HOSE, LENGTH AS PER YOUR
INSTALLATION.
• HOSE CLAMP FOR
5
/8” OD HOSE.
1. Measure the required length of drain tube from the bottom of
the humidifier to an appropriate floor drain.
2. Prepare the drain fitting at the rear of the water pan before
installing the water pan onto the furnace.
3. Referring to figure 26, first drill a small hole (
1
/8” dia) centered
from the bottom of the drain fitting up through the pan.
4. Then using a
3
/8” drill bit
carefully enlarge the hole to allow
for free flow of water.
5. Once the drain fitting has been
drill and the water pan installed
onto the furnace you may install
the drain tube (
5
/8”OD,
1
/2”ID)
not supplied.
6. First install a
5
/8” hose clamp
(not supplied) over the end of the
drain tube, then push the drain
tube up over the drain fitting and
secure in place with the hose
clamp. (Fig. 27)
7. Feed the other end of the drain
tube to a floor drain, secure to the
floor drain using a tie strap or
cable tie (not supplied).
::kitchensource.com Call 1-800-667-8721 anywhere in the US and Canada
Air King
at
::kitchensource.com
STEP #5: ELECTRICAL INSTALLATION
This unit is supplied with a 24 volt plug in transformer. The
transformer must be plugged into a constant (one that will not be
shut off) 120 volt outlet. The transformer is supplied with 10 feet
of low voltage wire which must feed the humidistat and the
humidifier’s drum motor. Select an outlet within the 10 feet.
HUMIDISTAT
The humidifier is supplied with an exclusive universal humidistat
which can be either wall mounted as furnished or, with a few
minor changes, be mounted on the return (cold) air plenum/duct.
Either wall mounting or plenum/duct mounting works equally
well for humidity sensing and control. Wall mounting provides
easy access to adjust the humidistat setting since it is located in
the living area. Plenum/Duct mounting provides a simple
installation (you should not have to purchase extra low voltage
wire or fish the wires through the wall).
WALL MOUNTING
1. Your humidistat is furnished in the “wall mounting” mode, no
changes to the humidistat are necessary, because the circuit is
low voltage (24 V), no switch box is required.
2. Select a location about five (5) feet above the floor on an inside
wall where normal air circulation exists. (In most residential
installations, the humidistat is installed near the heating
thermostat for easy adjustment and wiring.)
3. Because the humidistat will be located further away from the
humidifier you will have to purchase approximately 15 to 20
feet of 20 ga low voltage wire.
4. Drill a small hole in the wall and then fish the low voltage wire
out thru the hole. Leave approximately 6 inches of low voltage
wire leads outside the hole for humidistat connection.
5. Remove the cover plate
from the humidistat and
you will see four holes
at the corners of the
base plate mount the
humidistat on the wall
using the (4) 1” long
screws provided. Make
sure it is level and the
low voltage wire is
coming out thru the
3
/8”
hole on the base plate.
(Fig. 28)
6. Strip the low voltage wires and make connections to the
humidistat using the two 90˚ wire terminals provided. Replace
the cover plate.
7. Install the knob onto the humidistat control shaft.
PLENUM/DUCT MOUNTING
1. As shipped, the humidistat is ready for wall mounting. You
must first convert the humidistat from wall mounting to
plenum/duct mounting. The control mechanism must be in
the air stream in order to sense and control the humidity.
2. Remove the cover plate and discard it.
3. Remove the control
mechanism from the
base plate by removing
the two holding screws
at the back, and then,
turning the control
mechanism 180˚
upside down to allow
the shaft to protrude
out through the
1
/2”
hole on the base plate
(NOTE: base plate
remains in the same
position and only the control mechanism is turned (Fig. 29).
4. Replace the two screws to hold the control mechanism to the
base plate.
5. Attach the two 90˚ electrical terminals to the humidistat.
6. Use adhesive tape (not provided) to affix the humidistat
opening template to the pre-selected location and then drill
the 4 mounting holes and a
3
/8” hole in the area mark
humidistat cutout.
7. Using the
3
/8” hole as a starting point make the cutout cutting
on the outside of the line.
8. Skip to low voltage wiring section.
7
Furnace Humidifier
Figure 26
Figure 27
DRAIN FITTING
HOSE CLAMP
DRAIN HOSE
Figure 28
90˚ WIRE TERMINALS
FOR LOW VOLTAGE
WIRE CONNECTIONS
4 SCREWS PROVIDED
FOR MOUNTING TO
THE WALL
BASE
PLATE
KNOB
CONTROL
LABEL
COVER
PLATE
3/8” HOLE
Figure 29
HOLDING SCREWS
PRE-CUT
PLENUM
HOLE
CONTROL
MECHANISM
KNOB
CONTROL LABEL
BASE PLATE
SHAFT