Product Manual

- 22 -
Caution:
Wiring Option 2 and 3 are only allowed for split phase models (last letter of part # ā€œSā€). Wire all the
other models according to Wiring Option 1.
WARNING
For split phase models, AC input neutral is not required in wiring. Never Connect Input Neutral to
Output Neutral. Damage will result which is not covered under warranty. Always switch on the
inverter before plugging in any appliance.
WARNING
The output voltage of this unit must never be connected in its input AC terminal, overload or damage
may result.
The torque rating range for AC terminal is 12.5NM-16.5NM, and the suggested torque rating is
15.2NM. Over torqueing may cause the bolt to break. Use NO. 8AWG ,60ā„ƒ copper wires.
3.4 Grounding
Connect 8 AWG or greater copper wire between the grounding terminal on the inverter and the earth
grounding system or the vehicle chassis.