Do not loosen or touch the rear set screws on the terminal block.
Wiring Option 1
240V single phase / 120V single phase Input:
Ground + Hot line + Neutral Output: Neutral
+ Hot line + Ground
Wiring Option 2
240V split phase
Input: Ground + Hot line 1 + Hot line 2 - 240 Vac
Output: Hot line 1 + Hot line 2 + Neutral - 240
Vac
Wiring Option 3
240V split phase
Input: Ground + Hot line 1 + Hot line 2 - 240 Vac
Output: Hot line 2 +Neutral - 120 Vac
Note: In such case, each output hot line can only
carry a max of half the inverter's rated capacity.
Warning: If only using a 120V load, use Hot line
1 + Neutral. When the load power is more than
50% of the inverter’s rated capacity, use Hot line 2
+Neutral.
Option 1
Option 2
Option 3