Product Manual

12
Global LF Series Idle Power Consumption (in Watts)
Model NO Power Saver Off Power Saver On (3Secs)
PICOGLF10W12V120VR 12.5 7.5
PICOGLF15W12V120VR 13.5 8
PICOGLF20W12V120VR 28 12.7
PICOGLF20W24V120VR 26.5 12.2
PICOGLF20W48V120VR 28 12.7
PICOGLF30W12V120VR 55 21.7
PICOGLF30W24V120VR 46.5 18.9
PICOGLF40W12V120V 44.5 18.2
PICOGLF40W12V240VS 48 19.4
PICOGLF4012120240VS 48 19.4
PICOGLF40W24V120V 52.5 20.9
PICOGLF40W48V240VS 48 19.4
PICOGLF60W24V240V
76.8 29
PICOGLF60W48V120V
82 30
PICOGLF60W48V240V
80.7 30.3
When in the search sense mode, the green power LED will blink, and the inverter will make a
ticking sound.
At full output voltage, the green power LED will light steadily, and the inverter will make a steady
humming sound. When the inverter is used as an “uninterruptible” power supply the search sense mode or
“Power Saver On” function should be defeated.
Exceptions
Some devices when scanned by the load sensor cannot be detected. Small fluorescent lights and inductive
loads are the most common example. (Try altering the plug polarity by turning the plug over.) Some
computers and sophisticated electronics have power supplies that do not present a load until line voltage is
available. When this occurs, each unit waits for the other to begin. To drive these loads either a small
companion load must be used to bring the inverter out of its search mode, or the inverter may be
programmed to remain at full output voltage (Power On mode).
2.5.6 Protections
AC input over voltage protection/AC input low voltage protection
Low battery alarm/high battery alarm
Over temperature protection/overload protection
Short circuit protection (1s after fault)
Back feeding protection
When over temperature /overload occur, after the fault is cleared, the master switch needs to be reset
to restart the inverter.