Product Manual

11
When the power switch is turned to either “Power Save ON” or “Power ON”, the inverter is powered on.
The Power Saver function is designed to conserve battery power when AC power is not or rarely required
by the loads.
In this mode, the inverter pulses the AC output looking for an AC load (IE. electrical device). Whenever
an AC load (greater than 50-100 watts depending on model) is turned on, the inverter recognizes the need
for power and automatically starts inverting and output goes to full voltage. When there is no load (or less
than 50-100 watts depending on model) detected, the inverter automatically goes back into search mode to
minimize energy consumption from the battery bank.
In “Power saver on” mode, the inverter will draw power mainly in sensing moments, thus the idle
consumption is significantly reduced. The inverter will detect a load for 250ms every 3 seconds (DOP
switch#3 position 1).
Note: The minimum power of a load to take inverter out of sleep mode (Power Saver On) is 50 Watts for
inverters 1000-3000 watts and 100 Watts for 4000-6000 watts. The Global LF Series is designed with
extremely low idle power consumption, only a mere 0.8-1.8% of its rated power.