Product Manual
8
(determined by the Battery Type selection*). In this stage, the batteries are kept fully charged and ready if
needed by the inverter.
If the AC is reconnected or the battery voltage drops below 12Vdc/24Vdc, the charger will restart the above
cycle.
If the charge maintains the float state for 10 days, the charger will deliberately reset the cycle to protect the
battery.
Battery Type Selector
Switch setting Description Boost / Vdc Float / Vdc
0 Charger Off
1 Gel USA 14.0 13.7
2 AGM 1 14.1 13.4
3 AGM 2 14.6 13.7
4 Sealed lead acid 14.4 13.6
5 Gel EURO 14.4 13.8
6 Open lead acid 14.8 13.8
7 Lithium battery 14.4 14.4
8 De-sulphation 15.5 (4 Hours then Off)
9 Not used
For 24V X 2, for 48V X 4. (X= multiply)