Product Manual
www.aimscorp.net
6V 225Ah(10hr)
AGM6V225AH
proof. Usable in any orientation.
pressure build-up. The battery is completely sealed, maintenance-free, and leak
and oxygen, special one-way valves allow the gases to escape, avoiding excessive
immobilized. Should the battery be accidentally overcharged producing hydrogen
The dilute sulfuric acid electrolyte is absorbed by separators and plates and thus
The AIMS Power AGM maintaince free batteries are lead-acid dioxide technology.
31.4Ah(10hr)
Length(mm / inch) 320 / 12.6
Width(mm / inch) 176 / 6.93
Height(mm / inch) 225/ 8.86
Total Height(mm / inch) 230 / 9.06
Approx. Weight(Kg / lbs) 30.5 / 67.2
Nominal Voltage 6V
Design Life 10 years
Nominal Capacity 77
o
F(25
o
C)
10 hour rate (22.5A, 5.4V) 225Ah
Internal Resistance
Fully Charged battery 77
o
F(25
o
C)
3.2mOhms
Self-Discharge
o
Operating Temperature Range
Discharge
-20~60
o
C
Charge
-10~60
o
C
Storage
-20~60
o
C
Max. Discharge Current 77
o
F(25
o
C)
1000A(5s)
Short Circuit Current 3800A
Charge Methods: Constant Voltage Charge 77
o
F(25
o
C)
Maximum charging current 67.5A
Temperature compensation
-30mV/
o
C
Temperature compensation
-20mV/
o
C
page1 of 2
End Point
Volts/Cell
5 hour rate (39.2A, 5.25V) 196Ah
1 hour rate (147A, 4.80V) 147Ah
30min 1h 3h 5h 10h 20h
1.60V 224 147 58.8 41.2 23.0 11.9
1.65V 217 144 57.6 40.7 22.9 11.8
1.70V 209 141 56.4 40.0 22.8 11.7
1.75V 200 138 55.2 39.2 22.7 11.6
1.80V 192 134 53.6 38.3 22.5 11.5
30min 45min 1h 2h 3h 5h
1.60V
1.65V
1.70V
1.75V
1.80V
435 320 273 162 114 80.1
419 315 269 159 113 79.5
405 309 263 155 111 78.9
388 302 258 152 110 78.9
372 296 252 147 108 78.3
End Point
Volts/Cell
Cycle use 2.40-2.45VPC
Standby use 2.20-2.30VPC
Weight deviation: ± 3%
*
≤
Battery Construction
Component Positive plate Negative plate Container Cover Safety valve Terminal Separator Electrolyte
Raw material Lead dioxide Lead ABS ABS Rubber Copper Fiberglass Sulfuric acid
General Features
Performance Characteristics
No water filling.
No electrolyte maintenance.
for efficient gas recombination of up to 99%.
●
Absorbent Glass Mat (AGM) technology
●
Not restricted for air transport-complies
with IATA/ICAO Special Provision A67.
●
UL recognized component.
●
Can be mounted in any orientation.
●
Computer designed lead, calcium tin alloy
grid for high power density.
●
Long service life, float or cyclic
applications.
●
Maintenance-free operation.
●
Low self discharge.
●
●
Number of cells 3
3% of capacity loss per month at 20
C(average)
Discharge Constant Current(Amperes at 77° F 25° C)
o
o
Discharge Constant Power (Watts at 77°°° F 25° C)
oo
All data may be changed without notice.
(Note)The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.
Dimensions and Weight
20 hour rate (11.5A, 5.4V) 230Ah