Product Manual

Battery Construction
AGM12V100AH
Dimensions and Weight
Performance Characteristics
proof. Usable in any orientation.
pressure build-up. The battery is completely sealed, maintenance-free, and leak
and oxygen, special one-way valves allow the gases to escape, avoiding excessive
immobilized. Should the battery be accidentally overcharged producing hydrogen
The dilute sulfuric acid electrolyte is absorbed by separators and plates and thus
The AIMS Power AGM maintaince free batteries are lead-lead dioxide technology.
General Features
12V 100Ah(20hr)
Component Positive plate Negative plate Container Cover Safety valve Terminal Separator Electrolyte
Raw material Lead dioxide Lead ABS ABS Rubber Copper Fiberglass Sulfuric acid
Not restricted for air transport-complies
with IATA/ICAO Special Provision A67.
Recognized component.
Can be mounted in any orientation.
Computer designed lead, calcium tin alloy
grid for high power density.
Long service life, float or cyclic
applications.
Maintenance-free operation.
Low self discharge.
Length (mm / inch) 330 / 12.99
Width (mm / inch) 171 / 6.73
Height (mm / inch) 215 / 8.46
Total Height (mm / inch) 220 / 8.66
Approx. Weight (Kg / lb) 32 / 70.5
Nominal Voltage 12V
Number of Cells 6
Design Life 10 years
Nominal Capacity 77
o
F(25
o
C)
10 hour rate (9.50A, 10.8V) 95.0Ah
5 hour rate (17.4A, 10.5V) 87.0Ah
1 hour rate (65.2A, 9.6V) 65.2Ah
Internal Resistance
Fully charged battery 77
o
F(25
o
C)
5.7mOhms
Self-Discharge
3% of capacity loss per month at 20
o
C(average)
Operating Temperature Range
Discharge
-20~60
o
C
Charge
-10~60
o
C
Storage
-20~60
o
C
Max. Discharge Current 77
o
F(25
o
C)
900A(5s)
Short Circuit Current 2100A
Charge Methods: Constant Voltage Charge 77
o
F(25
o
C)
Maximum charging current 30A
Temperature compensation
-30mV/
o
C
Temperature compensation
-20mV/
o
C
page1 of 2
www.aimscorp.net
20 hour rate (5.00A, 10.8V) 100Ah
Cycle use 2.40-2.45VPC
Standby use 2.20-2.30VPC
Weight deviation: ± 3%
*
Discharge Constant Current (Amperes at 77
o
F 25
o
C)
Discharge Constant Power (Watts at 77
o
F 25
o
C)
End Point
Volts/Cell
10min 15min 30min 45min 1h 3h 5h 10h
1.60V 220 180 105 78.9 65.2 27.6 18.9 9. 75
1.65V 212 173 101 77.1 61.6 27.4 18.2 9. 70
1.70V 192 159 93.6 71.5 60.6 26.9 17.9 9. 65
1.75V 180 148 90.7 69.9 59.6 26.6 17.4 9. 60
1.80V 168 139 88.7 68.6 56.5 25.1 17.1 9. 50
End Point
Volts/Cell
10min 15min 30min 45min 1h 2h 3h 5h
1.60V 376 311 194 147 122 69.7 52.3 35.6
1.65V 364 306 183 143 116 66.9 50.7 35.2
1.70V 346 290 178 134 112 65.9 50.4 34.8
1.75V 339 285 173 131 109 63.7 48.6 34.2
1.80V 316 271 167 128 102 61.7 48.0 33.8
20h
5.20
5.15
5.10
5.05
5.00
(Note)The above characteristics data are average values obtained within
three charge/discharge cycles not the mimimum values.
All data may be changed without notice.
No water filling.
No electrolyte maintenance.
for efficient gas recombination of up to 99%.
Absorbent Glass Mat (AGM) technology

Summary of content (2 pages)