Specifications
19
N6700B MPS Mainframe
Regulatory
Compliance
EMC Complies with the European EMC directive 89/336/EEC for Class A test and
measurement products.
Complies with the Australian standard and carries the C-Tick mark.
This ISM device complies with Canadian ICES-001.
Cet appareil ISM est conforme à la norme NMB-001 du Canada.
Electrostatic discharges greater than 1 kV near the I/O connectors may cause
the unit to reset and require operator intervention.
Safety Complies with the European Low Voltage Directive 73/23/EEC and carries the CE-marking.
This product also complies with the US and Canadian safety standards for test
and measurement products.
Acoustic Noise
Declaration This statement is provided to Sound Pressure Lp < 70 dB(A),
comply with the requirements
*
At Operator Position,
*
Normal Operation,
*
According to EN 27779 (Type Test).
of the German Sound Emission Schalldruckpegel Lp <70 dB(A)
Directive, from 18 January 1991.
*
Am Arbeitsplatz,
*
Normaler Betrieb,
*
Nach EN 27779 (Typprüfung).
Isolation
No output terminal may be more than 240 VDC from any other terminal or chassis ground.
AC Input
Nominal Input Ratings 100 VAC – 240 VAC; 50/60/400 Hz
Input Range 86 VAC – 264 VAC
Power Consumption 1000 VA typical; 1100 VA maximum (with power factor correction)
Fuse Internal fuse (not customer accessible)
Mainframe
Dimensions
Height: 44.45 mm; 1.75 in.
Width: 432.5 mm; 17.03 in.
Depth: 596.9 mm; 23.5 in.
Mainframe
Weight
With 4 installed modules Net: 12.78 kg; 28 lbs.
Supplemental Characteristics (Continued)
Supplemental characteristics are not warranted but are descriptions of performance determined either by design or type testing.
All characteristics are typical unless otherwise noted.