Technical data
Command Reference 5
N9320A Programmer’s Guide 113
Set the Abs Stop
[:SENSe]:SEMask:OFFSet:LIST:STARt:ABSolute
<ampl>,...[<ampl>] (up to five values)
[:SENSe]:SEMask:OFFSet:LIST:STARt:ABSolute?
[:SENSe]:SEMask:OFFSet:LIST:STOP:ABSolute:COU-
Ple OFF|ON|0|1,...OFF|ON|0|1 (up to five values)
[:SENSe]:SEMask:OFFSet:LIST:STOP:ABSolute:COU-
Ple?
Enables you to enter an absolute level limit at Stop Freq for
the currently offset ranging from –200.00 to +50.00 dBm
with 0.01 dB resolution, and to toggle this function between
Couple and Man. If set to Couple, this is coupled to Abs Start
to make a flat limit line. If set to Man, Abs Start and Abs Stop
you can enter different values to make a sloped limit line.
*RST: Dependent upon Offset selected, please refer to the User’s
Guide for more details.
Range: –200 dBm to 50 dBm
Example: SEM:OFFS:LIST:STOP:ABS –20 dBm
SEM:OFFS:LIST:STOP:ABS:COUP 0
Key access:
> More > Spectrum Emission Mask > Offset/Limits > More >
Abs Stop
Set the Rel Stop
[:SENSe]:SEMask:OFFSet:LIST:STARt:RCARrier
<ampl>,...[<ampl>] (up to five values)
[:SENSe]:SEMask:OFFSet:LIST:STARt:RCARrier?
[:SENSe]:SEMask:OFFSet:LIST:STOP:RCARrier:COU-
Ple OFF|ON|0|1,...OFF|ON|0|1 (up to five values)
[:SENSe]:SEMask:OFFSet:LIST:STOP:RCARrier:COU-
Ple?
Enables you to enter an absolute level limit at Stop Freq for
the currently offset ranging from –150.00 to +50.00 dB with
0.01 dB resolution, and to toggle this function between
Meas