Product specifications

36
Power factor: 230 VAC single-phase option
3.3 kW models only: 0.99 at nominal
input and rated output power
208 & 400 VAC 3-phase options
3.3 kW models: 0.95 at nominal
input and rated output power
5 kW models: 0.94 at nominal input
and rated output power
Regulatory compliance: European EMC
directive 89/336/EEC for Class A
products, Australian C-Tick mark,
this ISM device complies with
Canadian ICES-001. Cet appareil
ISM est conforme à la norme NMB-001
du Canada. European Low Voltage
Directive 73/23/EEC.
Size: 88 mm H x 423 mm W x
442.5 mm D (3.46 in x 16.65 in x 17.42 in),
excluding connectors and handles
Weight: Net, 3.3 kW – 13 Kg (28.6 lbs);
5 kW – 16 Kg (35.2 lbs)
Warranty: One year
Ordering information
Opt 861 Unterminated line cord for 208 V
3-phase AC input voltage (Option 208)
Opt 862 Unterminated line cord for 400 V
3-phase AC input voltage (Option 400)
Opt 831 Unterminated line cord for 230 V
single-phase AC input voltage (Option 230)
Opt 832 Unterminated, harmonized line cord for
Europe for 230 V single-phase AC input voltage
(Option 230)
Opt 208 190-240 V, 3-phase AC, 50/60 Hz input
(use with line cord Opt 861)
Opt 400 380-415 V, 3-phase AC, 50/60 Hz input
(use with line cord Opt 862)
Opt 230 190-240 V, single-phase AC, 50/60 Hz
input (use with line cord Opt 831 or 832)
Accessories for all N8700 Models
N5740A Rack mount slide kit
(required for rack mounting; standard
system rack mounting hardware
will not work).
Single-Output 3.3-5.2 KW GPIB, LAN, USB
(Continued)
Spe cif icati ons
(at 0° to 55°C unless
otherwise specified)
More detailed specifications at
www.agilent.com/find/N8700
Basic DC Power Supplies essential features for a tight budget
N8759A N8760A N8761A N8762A
Number of outputs 1 1 1 1
GPIB No No No No
Output ratings
Voltage
1
100 V 150 V 300 V 600 V
Current
2
50 A 34 A 17 A 8.5 A
Power
5000 W 5100 W 5100 W 5100 W
Programming accuracy
Voltage
1
0.025%+ 75 mV 112.5 mV 225 mV 450 mV
Current
2, 6
0.1% + 150 mA 102 mA 51 mA 25.5 mA
Output ripple and noise
CV p-p (Up to 20 MHz) 100 mV 120 mV 300 mV 500 mV
CV rms (From 5 Hz – 1 MHz) 15 mV 25 mV 60 mV 120 mV
Measurement accuracy
Voltage 0.025%+ 125 mV 187.5 mV 375 mV 750 mV
Current
6
0.1%+ 150 mA 102 mA 51 mA 25.5 mA
Load effect
CV load regulation
3
20 mV 27.5 mV 50 mV 95 mV
CC load regulation
4
50 mA 34 mA 17 mA 8.5 mA
Source effect
CV line regulation
5
10 mV 15 mV 30 mV 60 mV
CC line regulation
5
25 mA 17 mA 8.5 mA 4.3 mA
Load transient recovery time
Time
7
<1 ms <2 ms <2 ms <2 ms
Supplemental Characteristics (Non-warranted characteristics determined by design and
useful in applying the product)
Output response time
Up-prog response time
8
50 ms 50 ms 50 ms 100 ms
Down-prog response time Full-load
8
100 ms 100 ms 100 ms 200 ms
Down-prog response time No-load
9
1500 ms 2000 ms 2500 ms 3000 ms
Remote sense compensation 5 V 5 V 5 V 5 V
Output ripple and noise
CC rms
10
100 mA 90 mA 30 mA 15 mA
Programming resolution
Measurement resolution
Voltage 12 mV 18 mV 36 mV 72 mV
Current 6 mA 4.1 mA 2 mA 1 mA
Notes:
1
Minimum voltage is guaranteed to maximum
0.2% of rated output voltage.
2
Minimum current is guaranteed to maximum
0.4% of rated output current.
3
From no-load to full-load, constant input voltage.
Maximum drop in remote sense.
4
For load voltage change equal to the unit voltage
rating, constant input voltage
5
Single-phase and 3-Phase 208 V models:
170~265 VAC, constant load. 3-Phase 400 V
models: 342~460 VAC, constant load.
6
The constant current programming readback
and monitoring accuracy does not include the
warm-up and load regulation thermal drift.
7
Time for output voltage to recover within 0.5%
of its rated output for a load change 10 - 90%
of rated output current, local sense.
8
From 10% to 90% or 90% to 10% of rated output
voltage, with rated, resistive load.
9
From 90% to 10% of rated output voltage.
10
For 8 V - 15 V models the ripple is measured from
2 V to rated output voltage and rated output current.
For other models, the ripple is measured at 10 - 100%
of rated output voltage and rated output current.