Product specifications

30
Supplemental characteristics
for all model numbers
Command processing time: Average time
required for the output voltage to begin
to change following receipt of digital
data is 55 ms.
DC floating voltage:
6 V to 60 V units
No output terminal may be more than
±60 VDC from any other terminal or
chassis ground
80 V to 600 V units
No output terminal may be more than
±600 VDC from any other terminal or
chassis ground
Modulation: (Analog programming
of output voltage and current)
Input signal: selectable,
0 to 5 V/0 to 10 V full scale
Input impedance: selectable,
0 to 5 kΩ/0 to 10 kΩ full scale
I/O interface: GPIB, LAN,
USB standard
Software driver:
• IVI-COM
• LabVIEW
AC input:
Input range: 85 – 265 VAC; 47 – 63 Hz
Input current 750 W: 10.5 A at 100 VAC
nominal; 5 A at 200 VAC nominal
Input current 1500 W: 21 A at 100 VAC
nominal; 11 A at 200 VAC nominal
Single-Output 750 W & 1500 W GPIB, LAN, USB
(Continued)
Spe cif icati ons
(at 0° to 55°C unless
otherwise specified)
More detailed specifications at
www.agilent.com/find/N5700
Basic DC Power Supplies essential features for a tight budget
N5761A N5762A N5763A N5764A N5765A N5766A
Number of outputs 1 1 1 1 1 1
GPIB, LAN, USB Yes Yes Yes Yes Yes Yes
Ouput ratings
Voltage 6 V 8 V 12.5 V 20 V 30 V 40 V
Current 180 A 165 A 120 A 76 A 50 A 38 A
Power 1080 W 1320 W 1500 W 1520 W 1500 W 1520 W
Programming accuracy
Voltage 0.05%+ 3 mV 4 mV 6.25 mV 10 mV 15 mV 20 mV
Current 0.1%+ 180 mA 165 mA 120 mA 76 mA 50 mA 38 mA
Output ripple and noise
CV p-p
(Up to 20 MHz) 60 mV 60 mV 60 mV 60 mV 60 mV 60 mV
CV rms
(From 5 Hz – 1 MHz) 8 mV 8 mV 8 mV 8 mV 8 mV 8 mV
Readback accuracy
Voltage 0.1%+ 6 mV 8 mV 12.5 mV 20 mV 30 mV 40 mV
Current 0.1%+ 540 mA 495 mA 360 mA 228 mA 150 mA 114 mA
Load regulation
(change from 10% to 90%)
Voltage 2.6 mV 2.8 mV 3.25 mV 4 mV 5 mV 6 mV
Current 41 mA 38 mA 29 mA 20.2 mA 15 mA 12.6 mA
Line regulation
(change from 85-132 VAC input
or 170-265 VAC input)
Voltage 2.6 mV 2.8 mV 3.25 mV 4 mV 5 mV 6 mV
Current 20 mA 18.5 mA 14 mA 9.6 mA 7 mA 5.8 mA
Transient response time
1
Time ≤ 1.5 ms ≤ 1.5 ms ≤ 1.5 ms ≤ 1 ms ≤ 1 ms ≤ 1 ms
Supplemental Characteristics
(Non-warranted characteristics determined by design
that are useful in applying the product)
Output response time
(settle to within ±1.0% of the
rated output, with a resistive load)
Up, full load 0.08 s 0.08 s 0.08 s 0.08 s 0.08 s 0.08 s
Down, full load 0.05 s 0.05 s 0.05 s 0.05 s 0.08 s 0.08 s
Down, no load 0.5 s 0.6 s 0.7 s 0.8 s 0.9 s 1.0 s
Remote sense compensation
Volts/load lead 1 V 1 V 1 V 1 V 1.5 V 2 V
Output ripple and noise
2
CC rms 360 mA 330 mA 240 mA 152 mA 125 mA 95 mA
Programming resolution/
measurement resolution
Voltage 0.72 mV 0.96 mV 1.5 mV 2.4 mV 3.6 mV 4.8 mV
Current 21.6 mA 19.8 mA 14.4 mA 9.12 mA 6 mA 4.6 mA
Notes:
1
Time for output voltage to recover within
0.5% of its rated output for a load change from
10 to 90% of its rated output current. Voltage
set point from 10% to 100% of rated output
2
From 5 Hz – 1 MHz, at 10% to 100% of output
voltage at full load (for 6 V units from 33% to
100% of output voltage)