Choosing AC Line Voltage and Cord Options for your Agilent Power Products
DC Power Supplies, DC Electronic Loads, and AC Sources (Continued)
Often, higher power products
(over 1 kW) are hardwired, i.e.
connected directly to a breaker
panel or distribution box. The
line cord may also be hard wired
to the back of the power supply
where a universal receptacle is
impractical. Typically, a local
electrician should be consulted
to determine the best alternative
to connect a high power product
to the AC line.
Cord 831 832 833 834
Options
Product/Family
No Plug #12AWG No Plug 4 mm
2
No Plug 1.5 mm
2
No Plug #10AWG
6030A, 31A, 32A, 35A 8120-5573 N/A 8120-5568 8120-5566
6571A - 75A 8120-5488 8120-5490 N/A 8120-5545
6671A - 75A 8120-5488 8120-5490 N/A 8120-5545
6812B 8120-5573 N/A 8120-5568 8120-5566
6813B 8120-5573 8120-6502 N/A 8120-5566
66000A 8120-5573 N/A 8120-5568 8120-5566
E4356A 8120-5488 8120-5490 N/A 8120-5545
N8731A-42A 8121-1949 8121-1331 N/A N/A
Cord 861 862 841 842
Options
Product/Family
No Plug No Plug NEMA IEC 309
(AWG) (Metric) 6-20P 32-A
N/S America, Asia, Europe, #12AWG 4 mm
2
(AWG wire) Harmonized N/S America Europe
(metric wire) Japan Korea
6030A, 31A, 32A, 35A N/A N/A 8120-5572 N/A
6571A - 75A N/A N/A N/A 8120-5489
6671A - 75A N/A N/A N/A 8120-5489
6680A - 84A 8121-6203 8120-6204 N/A N/A
6690A - 92A 8121-0694 8121-0695 N/A N/A
6812B N/A N/A 8120-5572 N/A
6813B N/A N/A N/A 8120-6506
66000A N/A N/A 8120-5572 N/A
E4356A N/A N/A N/A 8120-5489
N5761A-72A 8121-1330 8121-1331 N/A N/A
N8731A-62A 8121-1946 8121-1948 N/A N/A
E
L
N
E
E
L
N
E
L
N
N
L
E
L
N
E
N
L
X
Y
G
Option 848 Option 844 8120-5565 8418120-5489 8120-5567Option 845
8120-5565
W
L
G
E
L
N
E
E
L
N
E
L
N
N
L
E
L
N
E
N
L
X
Y
G
Option 848 Option 844 8120-5565 8418120-5489 8120-5567Option 845
8120-5565
W
L
G
High power products
There are several factors which
limit the amount of power which
can be readily drawn from a nor-
mal branch circuit. For example,
in the U.S., the typical 115/120 VAC
branch circuit has a circuit breaker
rated for 15 A. For industrial appli-
cations, 20 A service is commonly
available.
Linear power supplies with outputs
over 500 watts and switching
supplies rated over 750 watts will
generally exceed the capability of
a 15 A branch circuit. Connecting
power products above these power
levels will require installing either
a higher voltage or higher current
service. Some practical examples
are:
• standard line voltage for 2 kW
products such as the 667XA
is 230 VAC; they can not be
powered off a 120 VAC line
• the 1KW 601XA and 603XA
products cannot be powered off
a standard 15 A/120 VAC circuit;
they can operate off a 30 A/
120 VAC service, or they can
be configured for 208/240 VAC
operation
Agilent offers a range of 800 series
line cords for many higher power
products to mate with the wall
receptacles
commonly specified for
these higher
power services. Refer to
the tables to determine if there is a
800 series line cord for your prod-
uct with a plug that meets the local
requirements. If not, you must order
an unterminated line cord.